General operation
Seite/Page 148 Panel Generator Control P6+ RE0703_Kunde_eng.R06.1 - Kapitel/Chapter 11: General operation
10.5.11
With the Master-Slave-Adapter RE0706 two Generator Control Panels P6+ RE0703 can be connected to a Master-
Slave-Combination. In addition on each Generator Control Panel P6+ an Master-Slave-Adapter RE0706 is installed.
The Generator Control Panel P6+ is interconnected by the 14pole connecting terminals on the Master-Slave-Adap-
ters 1:1. The Master-Panel is hereby defined when the generator is connected to the main connector. Thus, the main
connector of the Slave-Panel should not be occupied (unconnected).
The solder jumpers on the Master-Panel have to be coded in the same manner as for a Master-Panel without a
Slave-Panel as in normal operation. The solder jumpers on the Slave-Panel are coded as for slave operation (please
see the appropriate adjustment pages for the Generator Control Panel P6+ RE0703).
The Master-Panel and Slave-Panel are identical, and only differs as a result of the coding. Both Master-Slave-
Panels are also identical.
11.8.3 Terminal Connections:
X2: (14polig, 21 - 34) master Slave connection (1:1 wire)
X3: (2polig, 35 - 36) 35: Panel on signal of the Generator Control Panel P6+ RE0703
36: Error signal of the Generator Control Panel P6+ RE0703
The Panel-ON-Signal is active when the panel is switched on.
The error signal is so long active, as the panel recognizes an error, which must lead to switching the generator off.
The output voltage corresponds to the operating voltage of the Generator Control Panel P6+ less 0,7V - 1,4V. Each
output has a free wheeling diode which short circuits externals voltage supplies under 0V and a decoupling diode
which decouples the circuitry from external power feeding.
11.8.4 Fuse:
A 0,8AT fuse must be installed on the Master-Panel.
11.8.5 Terminal connections
11.8.5.1 Terminal X2 ( IN/OUT from view Master-Opearating-Panel)
Fig. 11.8.5-1: Terminal connections terminal X2 (IN/OUT from the view of the master-control-panel)
Pin-No.
Pin-name
IN / OUT
Description
21
VBF
O
power (operation voltage behind fuse 12Vdc or 24Vdc depending on system)
22
GND
O
power supply - (ground)
23
ON-Signal
I / O
Panels are switched on, if the connection is switched using a push button (on master or slave) to
VBF
24
OFF-Signal
I / O
Panels are switched off, if the connection is switched using a push button (on master or slave) to
VBF
25
/Heat-Signal
I / O
Heat is active, if the connection is switched over a push button (on master or Slave) to GND
26
/Start-Signal
I / O
Start is active, if the connection is switched over a push button (on master or Slave) to GND
27
LED-T-Engine
O
Output for LED T-Engine on the Slave panel, is switched to GND, if the LED is illuminated
28
LED-Water-
leak (Replace
Airfilter)
O
Output for LED Waterleak on the Slave panel, is switched to GND, if the LED is illuminated
29
LED-Oil-
Press
O
Output for LED Oil-Press on the Slave panel, is switched to GND, if the LED is illuminated
Содержание 22-4 HD PVMV-N
Страница 8: ...Seite Page 8 Kapitel Chapter 2 10 5 11 12 Measurements 153 12 1 Hole pattern 153 ...
Страница 25: ...General Instructions and Regulations 10 5 11 Chapter 1 General Instructions and Regulations Page 25 ...
Страница 52: ...Seite Page 52 10 5 11 Leere Seite Intentionally blank The Panda Generator ...
Страница 94: ...Seite Page 94 Panda 8000 42NE PVMV N R01 10 5 11 Leere Seite Intentionally blank Maintenance Instructions ...
Страница 154: ...Seite Page 154 Panel Generator Control P6 RE0703_Kunde_eng R06 1 10 5 11 Leere Seite Intentionally blank Measurements ...