Generator control system
Based on VCS183
DS_VCS183
Page 16
Rev. 06
www.fischerpanda.com
©Fischer Panda generators Inc.
Data logging
Periodic and alarm data logging
During regular operation the control system will log one data set every 10 minutes or right before
initiating an emergency shutdown. These data sets are referred to as log memory (periodic logging) and
alarm memory (logged prior to an emergency-shutdown). Each memory has the capacity for a total of
150 such events. After logging event No. 150, the next log data will overwrite the first one, and so on.
Thus, always the last 150 events of each kind are available to the user via the panel. This allows a total of
1500 minutes (25 hours) of generator operation to be tracked.
Whether logging was initiated by regular (periodic) request or due to an alarm, the data that is logged is
always the same and listed below
Table 2: Log data set
Data
Unit
Control variable referencing generator control state machine. Internal usage only
n/a
Status feedback from VCS, as in byte stfeedback. Internal usage only
n/a
USB communication status
n/a
CAN communication status
n/a
Voltage L1-N, as sensed by the current sensing device
0.1V
Voltage L2-N, as sensed by the current sensing device
0.1V
Voltage L1-L2, as sensed by the current sensing device
0.1V
Current on Leg 1, as sensed by the current sensing device
0.1A
Current on Leg 2, as sensed by the current sensing device
0.1A
Frequency sensed by the current sensing device
0.1Hz
Active output power, calculated by the current sensing device
100W
Relative output power
0.1%
Power factor
0.001
Generator frequency sensed by VCS183
0.1Hz
Voltage L1-N, sensed by VCS183
0.1V
Battery voltage
10mV
Temperature coolant in
1°C
Current sensed on ground breaker output
0.01A
Cylinder head temperature
1°C
Exhaust elbow temperature
1°C
Coil temperature
1°C
Current sensing device temperature (average, 2 sensors in different locations)
1°C
Temperature on VCS183 control board
1°C
Alternator bearing temperature
1°C
Oil pressure
0.1bar
Relative tank content
1%
Engine speed
1rpm
Actuator voltage
10mV
Actuator current
10mA
Fuel pump current
10mA
Water leak ADC output
n/a
Operating time since last start
1min
Total el. Energy since last start
0.1kWh