Maintenance and cleaning 
 

Humidifier components are very easy to maintain. 
The following elements require maintenance: 

 

The irrigation pump: 

The most important thing is 

to  monitor  to  ensure  dirt  does  not  obstruct  the 
suction- 

impulsion 

circuit, 

and 

electricity 

consumption  is  below  the  power  rating  on  its 
plate. 

 

Control 

valves: 

These 

must 

be 

inspected  in  accordance  with  their 
mechanical regulation. 

 

Solenoid  valve: 

This  must  be  inspected  in 

accordance  with  its  mechanical  closure  and 
opening. 

 

Metal filter: 

This must be cleaned manually. 

 

Evaporative  panels: 

For  drinking  and  industrial 

water  supplies  their  operating  life  basically 
depends  on  the  constant  bleed-off  system  for 
mineral  salts  working  correctly  to  prevent  the 
formation of lime  deposits  on surfaces. If it  is not 
regulated properly, the panels have to be replaced 
in a short period of time, because the 
air passing through the panels becomes blocked by 
the formation of these deposits. 

 

Water tank: 

Elements holding bodies of still water 

are  renowned  for  generating  microorganisms,  and 
algae.  The  maintenance  director  must  implement 
an  inspection  plan  for  emptying  and  cleaning  the 
HEF-7  pump  tank  based  on  the  quality  of  the  air 
treated and the water supply. 

 

Regular observations are recommended for correct 
maintenance during the days following start-up, to 
find  out  how  the  specific  installation  is  behaving, 
and to 
establish  the  emptying  and  cleaning  programme. 
Similarly,  during  long  periods  of  inactivity  (summer  in 
the case 
of  humidification  for  comfort,  and  winter  for 
evaporative  refrigeration)  it  is  essential  to  totally 
empty and clean the tank. 

 

Evaporative  humidifiers  must  be  cleaned  on  a 
regular basis to prevent their contamination. All the 
surfaces  of  the  components  (panel,  pipes  and 
especially the water tank) must be disinfected using 
an appropriate solution. 

 

Element

 

Maintenance 
and Cleaning

 

 

 

IRRIGATION PUMP                           Monthly 

CONTROL VALVES                           Annually 

SOLENOID VALVES                          Annually  

METAL FILTER                                  Monthly  

EVAPORATIVE PANELS              Trimestralmente        

Quarterly WATER TANK               Trimestralmente     

 
 

Special attention must be paid to cleaning the piping system, 
and above all the junctions. 

 

In the case of the panels, the use of chemical disinfectants for 
daily  maintenance  is  not  recommended  because  it  could 
reduce panel efficiency and the useful life. If it is necessary to 
use chemical products, either because the system has 
not been operational for a long time, or for any other reason, 
an effective method is to submerge the panels in a chlorine 
disinfectant, such as sodium hypochlorite (bleach) or 
sodium percabonate. When using chlorine disinfectants, it is 
essential to take into account the formation of toxic  chlorine 
gas if it is combined with an acid solution. 

 

[Note]

 Do not forget to employ the safety measures 

of the manufacturer of the disinfectant solution.

Содержание HEF7 Series

Страница 1: ...6 info fisair com fisair com HEF7 SERIES INSTALATION AND MAINTENANCE MANUAL Adiabatic cooling system for Air condensed Water Chillers MHEF7 EN 21 0 In compliance with European Union standards for mach...

Страница 2: ...HEF7 series manual 2...

Страница 3: ...ion 19 10 Level detector connection 20 11 Solenoid valve electricity connection 22 12 Connection of the motor zone valve N C for automatic emptying draining 23 13 Setting the valve regulating irrigati...

Страница 4: ...are laid out in criss crossing channels to provide a large surface area for air water contact which maximizes water evaporation and at the same time minimizes resistance to the air flow passing throu...

Страница 5: ...amiliar with it before installing commissioning or servicing The following symbols or messages may appear in this document or on the equipment They warn of potential hazards or provide information tha...

Страница 6: ...not be removed or disabled Installing Disassembling Maintaining and Repairing the unit The machine must not be manipulated when it is operating Switch off the unit s power supply when conducting maint...

Страница 7: ...manual 7 2 HEF7 nomenclature HEF7 MODEL HEF7 VCS906 E6 Factory chiller model PUMPING GROUP FOR HEF7 Pumping group 230V IN 50 60Hz Line voltage Basic control panel CONTROL PANEL CCB2 0 230V IN 50 60Hz...

Страница 8: ...ed into or assembled with other machinery or other partly completed machinery or equipment thereby forming machinery to which this Directive applies Therefore the HEF7 device is classified according t...

Страница 9: ...HEF7 series manual 9 Machine type rating plate Partly completed machinery quasi machine type rating plate...

Страница 10: ...m the evaporation Maximum freshness it works as a natural filter purifying the entry air Carefully designed channelling eliminates dust particles and mineral deposits from the air which are trapped on...

Страница 11: ...ation and cooling even at high air speeds They are made of fireproof inorganic material They are ideal for humidifiers placed after air treatment and heater units and for the pre cooling of gas turbin...

Страница 12: ...HEF7 series manual 12 5 Unit components 1 2 4 3 7 5 6...

Страница 13: ...Cassette length H Cassette height E Cassette thickness For further information on parts of systems please contact the manufacturer Brand Code Descriptions Units 1 REGULATION VALVE 1 2 62000075 REGULAT...

Страница 14: ...Supply B Constant bleed off C Overflow D Drainage 1 Regulation valves with Flow meter Irrigation 2 Regulation valves with Flow meter Bleed off 3 Filling Solenoid Valves 4 Max Min level detector 5 Valv...

Страница 15: ...VICING SPACE Humidifiers are normally placed just before the coil and before the sensible exchange in the air cooling system A 1m space should be left in front of the unit section for inspection and s...

Страница 16: ...ollowing table Before drying the evaporation panel the ventilation must be stopped for 10 minutes and watering continued with the cassettes This is done by keeping the water recirculation or direct wa...

Страница 17: ...etwork supply to the filter in Y and this to the solenoid supply valve Connect the common outlet for the 50mm diameter drain overflow constant bleed off to the drainage network The water outlet connec...

Страница 18: ...he main water supply line with continuous water flow 2m Install a 3 way valve before the cut off valve with a return line to the main water supply line to avoid water retention o If the distance from...

Страница 19: ...ricity supply cable to the terminal box of the water irrigation pump using an appropriate connection IP 55 or higher La protecci n y operativa de alimentaci n el ctrica a la bomba debe ser determinada...

Страница 20: ...it to this level so that it is cut for safety J16 sensor indicates maximum water level NC take a look on CCB2 0 manual Remark Max Voltage 175 Vcc 110 Vca Max Current 1 Acc Temperature 20 120 C Min De...

Страница 21: ...be left without connection Mesh to fix the float Remark Remove the fixing mesh when the equipment is placed on its final location just before commissioning N C normally closed ALTO High level S2 N A n...

Страница 22: ...NC solenoid valve of the tank is composed of the body of the valve the coil and the connector The coil and the connector are supplied for a 24Vac or 230Vac connection G brass water supply N C solenoid...

Страница 23: ...C for automatic emptying draining Remark When this motor zone valve is connected to the CCB2 0 Basic Control Panel it will be necessary to connect the S4 cables Black Red and S6 ones Black Pink to the...

Страница 24: ...HEF7 series manual 24 GMA12 1 GMA32 1 2 points control AC 24 V 2 points control AC 230 V Dimensions Electric Diagram connections...

Страница 25: ...24 V DC 24 48 V G0 2 black BK System neutral Actuators AC 230 V L 3 brown BN Phase AC 230 V N 4 blue BU Neutral conductor Auxiliary switch Q11 S1 grey red GY RD Switch A input Q12 S2 grey blue GY BU S...

Страница 26: ...lowing equation for calculating the total irrigation flow of each HEF 7 can be employed to set the regulation valve precisely n I e 60 ai i 0 I total unit irrigation e thickness of the evaporative cas...

Страница 27: ...ppm pH 6 8 Silica SiO 30 ppm Iron Fe 0 2 ppm Oils and grease 2 ppm Total dissolved solids 550ppm Total alkalinity CaCo3 50 170 ppm Suspended solids 5 ppm Bleed off based on the cycle of concentration...

Страница 28: ...by removing the handwheel from its parked position and placing it on the flow meter It can then be swivelled to set the required flow Once the flow has been set place the handwheel in its parked posit...

Страница 29: ...ng air flow contamination and avoid extra foam formation it is recommended to repeat the following cycle for 6 periods 10 min of pump operation recirculating the water and then 10 min of emptying Rema...

Страница 30: ...umidifiers work with water temperatures below 24 C very far from the optimal growth temperatures of the bacteria present in the water essentially Legionella pneumophila with an optimum growth temperat...

Страница 31: ...tants are used they should not be mixed with an acid solution due to the potential formation of toxic chlorine gas Remark The manufacturer s safety steps for the disinfectant solution should be follow...

Страница 32: ...days following start up to find out how the specific installation is behaving and to establish the emptying and cleaning programme Similarly during long periods of inactivity summer in the case of hu...

Страница 33: ...hly recommended practice is to add water treatment to the humidifier supply In order to remove the evaporative cassettes from the units it is necessary to take off the upper front cover of the structu...

Страница 34: ...17 Machine conformity declaration...

Страница 35: ...18 Cuasi machine conformity declaration...

Страница 36: ...19 WARRANTY...

Страница 37: ......

Отзывы: