First UNI TEMP Series Скачать руководство пользователя страница 5

www.first.si

4

UNI TEMP 

1

ON

2 3 4

DIP switch settings

CW

Temperature 

range setting

x10

CCW

x1

1

2

3

4

min

max

DIP

0

°

C..100

°

C

60

°

C..85

°

20

°

C..70

°

C 25

°

C..45

°

C

2

OFF

OFF

ON

ON

3

OFF

ON

OFF

ON

Temperature range setting

1

ON

2 3

4

Xp parameter 

a proportional control 

range of valve

UNI TEMP 

www.first.si

Manual control:

Note: 

when the button 

for manual operation is 
in <MAN> position, 
controller stays in 
temporary position 
irrespective of control 
signal.

Controller behavior diagram as a function of temperature:

50

45

45°C

50°C

55°C

55

permanent 

valve opening

permanent 

valve closing

set temperature

T (°C)

t

closing area

100% opening

100% closing

opening area

T

50

=

set

°C

Xp =10K

Xp = 10K

permanent 

valve opening

permanent 

valve closing

impulse valve 

opening

impulse valve 

closing

Example:

-

Desired temperature: 50 C

-

Xp parameter – proportional control range of valve (10K)

°

When the temperature is 
less than 45

, controller 

gives continuous signal 
for opening mixing valve.

°C

When the temperature is 
between 45

 and 50

controller pulsating 
opens mixing valve. 
Nearer the desired 
temperature (50

), 

shorter pulses.

°C

°C

°C

When the temperature is 
between 50

 and 55

controller pulsating 
closes mixing valve.
Nearer the desired 
temperature (50

), 

shorter pulses.

°C

°C

°C

When the temperature is 
higher than 55

controller gives 
continuous signal for 
closing mixing valve.

°C

Nearer the desired 

temperature (50

), 

shorter pulses.

°C

Nearer the desired 
temperature (50

), 

shorter pulses.

°C

impulse valve 

opening

impulse valve 

closing

www.first.si

4

UNI TEMP

Settings:

With DIP switches inside actuator is 
possible to set the following 
parameters:

DIP 1

Direction of rotation (direct CW / 
inverse CCW)

DIP 2,3 Different temperature ranges 

depending on the application 
(0°C..100°C, 60°C..85°, 20°C..70°C, 
25°C..45°C)

DIP 4

Reaction factor

NOTE – when changing DIP1 position, 
controller calibration is carried out

ON

1 2 3 4

DIP switch settings

ON

1 2 3 4

LED

COM

Xp

Trimmer Xp is located inside controller. 
To open the controller it is necessary to loosen the 
screws on the cover (3x), and handle screw (1x).

Xp parameter - a proportional control range of 
valve (from 10K to 100K)

Xp parameter - a proportional control range of valve (from 10K to 100K)

1 Mechanical  indication.

Indicator can be set according to the valve 
assembly

2 Button for manual/auto control

3 Handle for manually controlling the drive, which 

also serves for the indication position of the valve

4 Button for adjusting the required temperature. 

When adjusting the temperature, the set value 
flashes on LCD screen.

5 LED indication of:

- Flash: actuator calibration
- ON: normal operation

6 LCD screen for displaying temperature

7 DIP switches cover

90°

Содержание UNI TEMP Series

Страница 1: ...ithout valve Enclosed mounting kit FIR T ROTOMIX ROTOMIX G ESBE VRG VRB ACASO TERMOMIX BARBERI FEROTERM PAW EURONORM ESBE IMP DANFOSS BESSER SELTRON LOVATO TUXHORN STRAWA CIMBERIO UNI TEMP is a consta...

Страница 2: ...OMIX ROTOMIX G ESBE VRG VRB ACASO TERMOMIX BARBERI FEROTERM PAW EURONORM ESBE IMP DANFOSS BESSER SELTRON LOVATO TUXHORN STRAWA CIMBERIO 24V 50Hz UNI TEMP 24VAC UNI TEMP 230VAC 40 6 l 1 5m Sensor VF KT...

Страница 3: ...t 58024 G ESBE VRG VRB ACASO TERMOMIX BARBERI FEROTERM PAW EURONORM ESBE IMP DANFOSS BESSER SELTRON LOVATO TUXHORN STRAWA CIMBERIO By special request 58025 SELTRON LOVATO PAW 58026 LAZZARI LANDIS 5802...

Страница 4: ...libration is carried out ON 1 2 3 4 DIP switch settings ON 1 2 3 4 LED COM Xp Trimmer Xp is located inside controller To open the controller it is necessary to loosen the screws on the cover 3x and ha...

Страница 5: ...red temperature 50 C Xp parameter proportional control range of valve 10K When the temperature is less than 45 controller gives continuous signal for opening mixing valve C When the temperature is bet...

Страница 6: ...heat reservoir UNI TEMP UNI TEMP UNI TEMP UNI TEMP UNI TEMP DTC100 2 M Examples UNI TEMP Maintain a constant temperature in sanitary water circuit Floor heating Maintain a constant temperature of hea...

Страница 7: ...and the technical data of the product without prior notice Safety notes The actuator has been designed for use in stationary heating ventilation and air conditioning systems and is not allowed to be...

Отзывы: