DTC 200

TERMINAL  CONNECTION 

1,2 

sensorT1 – heating source (collector, boiler, …) 

2,3 

sensor T2 – hot water tank  

11 

N – not in use 

12 

L - not in use 

13 

N - neutral 

14 

L - phase - pump 6(1)A, 250V   , 50Hz 

15 

L – phase mains 230V   , 50Hz 

16 

N – neutral mains 230V   , 50Hz 

 

 
 

 

 

 

1.5 EXAMPLES OF USE
example: 1

Heating sanitary water with solar collectors.

6(1)A, 250V

Grounding wires should
be connected to special
terminal pins situated on
left side of terminal strips.

The thermostat is
designed for fixed

installation. When per-
forming electric installa-
tion, an element should be
inserted which enables at
least 3 mm separation of
thermostat from the mains
(switch or socket). Prior to
each intervention in the
thermostat, first disconnect
it from the mains.

ELECTRIC CONNECTION

Before each intervention in the thermostat first discon-
nect the main power!

DTC 200/ (2 sensors)

1. Heating the domestic hot water from one heating source
(solar collectors, boilers, heat pump...) .

1.1 Basic

Differential thermostat controls the electric motor actuated ball
valve (EMV 110..) and the circulation pump.
The thermostat enables setting of two parameters:
1. Regulation of maximum temperature in hot water tank from
10° to 90°C.
This temperature is defined by T2 sensor witch is generally
mounted in upper third of heat exchanger.
2. Regulation of difference for exchanger from 0K to 15K.
With these regulation you define how much the value of the
source temperature (collector, boiler,...) should exceed the tem-
perature of water around the exchanger in hot water tank, that
the thermostat opens the valve and activates the pump.
The difference is set in relation to the volume of heat losses of
the system which depend on lengths of pipelines from source
to hot water tank and on pipeline insulation.

SENSORS INSTALLATION

T1 AND T3 SENSORS INSTALLATION IN TO SOLAR
COLLECTOR OR BOILER:

Use KF sensors with silicon cable insulation  (RED
colour)!

Install it as immersion sensor in collecting pipe at the top of the
collectors or boiler in provided sleeve. Connect sensors on the
terminals 1 and 2. Use sensors KF with red silicon cable and
use cable type J-Y (St) 1X 2X0,6 for connection.
For cables longer than 15m we recommend over-voltage pro-
tection with VDR resistor. For over voltage protection is recom-
mended use of armoured cable and it must be earthed.

flow direction

T-piece 1/2”

pipe1/2”

VDR resistor thermo-shrinkable

tubes

sensor kable

extension cable

T2 AND T4 SENSORS INSTALLATION IN DOMESTIC HOT WA-
TER TANK (DHWT):

Use BSF1 sensors with PVC cable insulation  (GRAY
colour)!

Install T2 sensor to provided place in hot water tank or on hot water
tank wall under isolation as contact sensor in upper part of ex-
changer. When sensor is mounted as contact one we recommend
to coat it with heat conducting paste or liquid metal. Use sensors
BSF1 with PVC cable.

In special purpose vertical or horizontal
tube (sensor should be protected against
accidental extraction).

On hot water tank with clip, wire and
spring strip (use paste for better heat
transmission).

WARNING!
At mounting protect sensors against ambient influence and
assure suitabile mechanical protection.

1.2 Operation

DTC 200 works as single differential thermostat, which mea-
sures the temperature of heating source (collectors, boiler, ...)
and in user (hot water tank).
Heating effect is provided, when heating source temperature is
higher than the temperature of the user (water in hot water
tank). Consequently minimum difference should be 3K-5K. Rec-
ommendable minimal value is 5K.
When the temperature of the source exceeds the temperature
around the user for pre-set difference opens the electric motor
actuated ball valve and switches the pump.
The thermostat switches off the pump if pre-set temperature is
reached in hot water tank (adjustable from 10° to 90°C).

Содержание DTC 200

Страница 1: ...se 2 DTC 200 3 sensors 5 2 1 Basics 2 2 Operation 2 3 Electrical connection 2 4 Examples of useji 3 DTC 200 4 tipala 7 3 1 Basics 3 2 Operation 3 3 Electrical connection 3 4 Examples of use WARNING In...

Страница 2: ...Outputs 2relayoutputs 230V 50Hz 6 1 A WorkingcontactSPST controlling the electric motor actuated ball valve and pump Inputs 4 sensors BSF1 PVC cable 1 5m long DHWT sensor KF silicon cable 2m long coll...

Страница 3: ...ad cables into the thermostat housing like as shown on the picture On one side lead the sensor cables and on the other the rest With two discharger screw the cables very tight to prevent the extractio...

Страница 4: ...water tank and on pipeline insulation SENSORS INSTALLATION T1 AND T3 SENSORS INSTALLATION IN TO SOLAR COLLECTORORBOILER Use KF sensors with silicon cable insulation RED colour Install it as immersion...

Страница 5: ...on in the thermostat first disconnect it from the mains Before each intervention in the thermostat first discon nect the main power ELECTRIC CONNECTION the thermostat opens the valve and activates the...

Страница 6: ...itary water with solid fuel boiler into one hot water tank with two exchangers Example 5 Heating hot water in two water tanks with solar collectors Example 6 Heating sanitary water with solid fuel boi...

Страница 7: ...n the temperature of the source exceeds the temperature around the exchanger for set difference the thermostat opens the valve EMV110 and activates the pump Thermostat closes the valve and switch of p...

Страница 8: ...or actuated ball valve EMV 110 series 602 502 12 2W Electric motor actuated ball valve EMV 110 series 602 502 Instead of the electric motor actuated ball valves 10 and 12 you can use non return valves...

Отзывы: