background image

 

 

 

brkelectronics.com

A R C H I T E C T U R A L   A N D   E N G I N E E R I N G   S P E C  

I N S T A L L A T I O N   O F   A L A R M

The smoke/CO combination  alarm shall be a First Alert Model SCO5 and shall provide 
at a minimum the following features and functions:
  1.  A Photoelectric smoke sensing chamber and an electrochemical CO sensor.
  2.  The unit shall have a lower and varying horn frequency to to make it easier for  
 

 the elderly with normal age related hearing loss to better hear the horn

  3.  Fully screened smoke sensing chamber to resist entry of small insects thereby  
 

 reducing the probability of unwanted alarms and be capable of self restoring.

  4.  Powered by supervised 2 AA alkaline batteries and a solid state piezo horn rated at  
 

 85dB at 10 ft.

  5.  A visual green LED power-on indicator to confirm unit is receiving power. A visual  
 

 red indicator to show unit is alarm.

  6.  A full function test button should check all alarm functions by simulating a smoke  
 

 and CO condition, causing the unit to alarm.

   7.  Two Silence features - Low Battery Silence: Silence low battery chirp for up to 8  
 

 hours. Alarm Silence: Temporarily silence unwanted nuisance alarms.

  8.  Optipath 360 Technology

TM

 - provides 360 degrees of direct access to the    

 

 smoke sensing chambers.

  9.  Two Locking features - tamper resistant locking pins that lock battery drawer  
 

 and/or alarm to mounting bracket.

 10.  The unit shall be capable of operating between 40°F (4°C) and
 

 100°F (38°C) and relative humidity between 10% and 95%.

 11.  The unit shall contain mounting hardware and shall be listed for wall
 

 or ceiling mounting.

 12.  The unit shall at a minimum meet the requirements of UL217, UL2034, CSFM,
 

 NFPA 72, NFPA 720, NFPA 101, ICC

Installation of this alarm must conform to NFPA 72 and NFPA 720. Always check your local 
building codes. Follow all instructions for placement as outlined in the user’s manual.

S H I P P I N G   S P E C S :

T E C H N I C A L   S P E C S

Individual Carton Dimensions  

5.13 ”L x 2.380”W x 5.13”H

   Weight  

0.66lbs.

   Cube  

0.036 ft3

   UPC  

0 29054 00347 8 (SCO5B)

 

0 29054 00304 1 (SCO5LB)

Master Carton Dimensions  

10.750”L x 7.880”W x 11.06”H

Master Pack 

12 

  Weight  

8.4lbs.

   Cube  

0.542 ft3

   I2 of 5  

700 29054 00347 7 (SCO5B)

 

100 29054 00304 8 (SCO5LB)

Pallet Information  

   Cases per Layer 

22 

   Number of Layers 

4

   Cases per Pallet  

88

   Units per Pallet  

1,056

   Cube 

53.9 ft3

   Weight 

804 lbs.

©2009 BRK Brands, Inc. a Jarden Corporation 
Company (NYSE: JAH)

3901 Liberty Street Road
Aurora, IL  60504-8122
All rights reserved

First Alert is a registered trademark of the First Alert Trust
BRK is a registered trademark of BRK Brands, Inc.
CM2954

CAT. 

SCO5B Series

THE PARTS OF THIS SMOKE/CO ALARM

 

 

BOTTOM OF ALARM

  1.  

Mounting bracket

  2.  

Mounting Slots

  3.  

Battery Drawer - Install

 

 

2 AA batteries here

  4.  

Turn this way to 

 

 

remove from bracket

   5.  

Turn this way to 

 

 

attach to bracket

 

 

TOP OF ALARM

 

1.   Test/Silence button &     

            remote control sensor

 2. 

 

Slide-open

  

battery 

drawer

 

3.   Power/smoke alarm light

 

4.  CO alarm light

BATTERY DRAWER LOCK

 

Remove Pin from 

Mounting Bracket

 

Close Door. Insert Pin in Holes 

through alarm and Battery Drawer

5.0"

TOP VIEW

SIDE VIEW

MOUNTING

BRACKET

2.0"

 

 

 

Alarm Dimensions:  

5.0” dia x 2.0”H

Weight:  

8.4 oz.

Operating Voltage:  

2AA Alkaline Battery Powered

Temperature Range:  

40°F (4°C) to 100°F (38°C)

Humidity Range: 

10% to 95% relative humidity (RH)

Audio Alarm: 

85dB at 10 feet

Test/Silence: 

Electronically simulates smoke and CO conditions,  

 

 

causing the unit to alarm and temporarily silence the alarm         

   Remote: 

Use vol/chn buttons on most household IR remotes.

   Manual: 

Press and hold test/silence button

Alarm Reset: 

Automatic when smoke and/or CO clears

Smoke Sensor: 

Photoelectric

CO Sensor: 

Electrochemical

Indicator Lights/Sounds:

   DC Power: 

Intermittent Red Light

   Alarm: 

Audio Alarm, rapidly flashing red light by corresponding   

 

smoke or CO indicator light

Listing: 

Listed to UL217 and 2034 Standards

Отзывы: