Figure 2 – FA570CR Wiring Details
SETTING THE KEYPAD ADDRESS
The keypad address must be set according to the control
panel being used (refer to the individual control panel’s
instructions for details). Available addresses are 00
through 30. The keypad is shipped with a default address
of 31 (non-addressable mode). To change the address, do
the following:
1.
Enter keypad address mode:
Power up the keypad. Within 60 seconds of power-up,
press and hold down the [1] and [3] keys together for 3-
seconds. The current address will be displayed and the
cursor will be under the “tens” digit (
31
).
Notes:
•
If the system has been powered up for more than 60
seconds, you must power the keypad down, and then
power it up again in order to change the keypad’s
address.
•
The keypad will not enter the address mode if the
system is in the program mode.
•
If 10 seconds have passed with no key entry, the keypad
automatically exits the address mode.
FOR WARRANTY INFORMATION AND LIMITATIONS OF THE ENTIRE
SYSTEM, REFER TO THE INSTALLATION INSTRUCTIONS FOR THE
CONTROL PANEL WITH WHICH THIS DEVICE IS USED.
2.
Set the desired address:
Enter the desired address. For example, for address 12,
enter 1, then 2. Display shows (12).
3.
Exit the address mode:
Press the “star” key
(
✻
)
to save the displayed address
and exit the address mode. The current address may be
viewed at any time by pressing and holding [1] and [3]
keys together.
KEYPAD LABELS
Function key labels:
A set of adhesive-backed labels
with some typical function symbols (e.g., fire, police,
emergency, etc.) is provided. These labels come in four
colors (red, blue, green, and white) and may be placed on
the appropriate function keys (A, B, C, or D) for ease of
identifying the individual key’s function (as determined by
the control panel’s capability and programming).
OPERATING THE KEYPAD
For operating instructions, see the User Guide for the control
panel used with this keypad.
SPECIFICATIONS
Physical:
5.25” H x 7.437” W x 1.312” D
Display:
Alphanumeric, 32-character (2 lines x 16
characters), LCD back-lit
LEDs:
ARMED (red), READY (green), POWER
(green), FIRE ALARM (red) *SUPER-
VISORY (yellow) and *TROUBLE (yellow)
* Refer to the control panel’s instructions
for specific applications regarding Trouble
and Supervisory LEDs.
Sounder:
High-quality
speaker
Electrical:
Voltage: +12VDC (from power-limited
source)
Current: 50mA standby;
160mA in alarm (sounder, back
light and LEDs on)
NFPA-72
Compliant