Firman H05753 Скачать руководство пользователя страница 20

Page 18

Grounding

The National Electric Code requires your generator 
must be properly connected to an appropriate 
ground to help prevent electric shock.

Failure to properly ground the 
generator can result in electric 
shock.

WARNING

THERE IS A PERMANENT CONDUCTOR BETWEEN 
THE GENERATOR (STATOR WINDING) AND THE 
FRAME.

Use approved transfer equipment to prevent 
backfeed by isolating generator from electric 
utility workers.
When using generator for backup power, notify 
utility company.
Use a ground fault circuit interrupter (GFCI) in 
any damp or highly conductive area, such as 
metal decking or steel work.
DO NOT touch bare wires or receptacles.
DO NOT use generator with electrical cords 
which are worn,frayed, bare or otherwise 
damaged.
DO NOT operate generator in the rain or wet 
weather.
DO NOT handle generator or electrical cords 
while standing in water, while barefoot, or 
while hands or feet are wet.
DO NOT allow unqualified persons or children 
to operate or service generator.

Connecting to a Building's Electrical System

WARNING

Generator voltage could cause 
electrical shock or burn resulting 
in death or serious injury.





English                                                                                                                                                  Customer Service: 1-844-FIRMAN1

Содержание H05753

Страница 1: ...and level before performing any maintenance or service IMPORTANT Record product information to reference when ordering parts or obtaining warranty coverage Serial Number DUAL FUEL GENERATOR MODEL NUMB...

Страница 2: ...tion Connecting to a Building s Electrical Maintenance And Storage 27 Maintenance Schedule 27 Engine Maintenance 28 Change Engine Oil 28 Air Filter Maintenance 28 Spark Plug Maintenance 29 Cleaning Fu...

Страница 3: ...mation The manufacturer cannot possibly anticipate every possible circumstance that might involve a hazard The warnings in this manual and the tags and decals affixed to the unit are therefore not all...

Страница 4: ...SAFETY PRECAUTIONS Page 02 WARNING POISONOUS GAS HAZARD English Customer Service 1 844 FIRMAN1...

Страница 5: ...de and downwind far away from windows doors and vents Direct exhaust away from occupied spaces INCORRECT USAGE Do not operate in any of the following locations Near any door window or vent Garage Base...

Страница 6: ...OR DRAINING GASOLINE Turn generator engine OFF and let it cool at least 2 minutes before removing fuel cap Loosen cap slowly to relieve pressure in tank Fill or drain fuel tank outdoors DO NOT overfi...

Страница 7: ...T handle generator or electrical cords while standing in water while barefoot or while hands or feet are wet DO NOT allow unqualified persons or children to operate or service generator WARNING Exhaus...

Страница 8: ...Gasoline can cause a fire or explosion if ignited Gasoline is a liquid fuel but it s vapors can ignite Gasoline is a skin irritant and needs to be cleaned up immediately if spilled on skin or clothes...

Страница 9: ...CAUTION LPG under pressure is highly flammable and can cause a fire or explosion if ignited LPG is heavier than air and can accumulate in confined spaces and low places in the event of a leak LPG has...

Страница 10: ...he axle pin A through the wheel B 3 Slide the axle pin A through the mount point on the frame and flat washer D 4 Secure the wheel and axle pin with the cotter pin C 5 Repeat steps 2 4 to attach anoth...

Страница 11: ...nnection NOTE The generator comes equiped with the positive red and negative black cables already attached to battery terminals 1 Cut wire tie that is binding the black battery cables A and B 2 Insert...

Страница 12: ...OHV Engine 7 Recoil Starter 8 10 0 Flat Free Wheel 9 10 11 12 13 Oil Filler Cap Battery Outlet Cover Control Panel Handle 14 LPG Hose Connector Inlet 15 Hose Holder 16 LPG Hose with Regulator English...

Страница 13: ...t will become RED up to 4 minutes before goes off Starting the engine successfully during these 4 minutes will turn the indicator light GREEN MUST HAVE SOLID RED INDICATOR LIGHT TO BE ABLE TO START TH...

Страница 14: ...RMAN1 9 10 11 Outlet Cover Protect the receptacles from dust and debris LPG Hose Connector Inlet Used to connect LPG hose to generator 120 240V 30A Twist Lock NEMA L14 30R Maximum 30 Amp current maybe...

Страница 15: ...1L Counter Clockwise Facing P T O Float Brushed Polyurethane Type Yes 5700 GASOLINE 5700 LPG FIRMAN Rated Fequency 60Hz Oil Type See Add Engine Oil Section AN IMPORTANT MESSAGE ABOUT TEMPERATURE When...

Страница 16: ...l activate a warning device or stop the engine If generator shuts off and the oil level is within specifications check to see if generator is sitting at an angle that forces oil to shift Place on an e...

Страница 17: ...d fuel fill cap remove cap 2 Slowly add unleaded fuel to fuel tank Be careful not to fill above the red fuel level indicator This allows adequate space for fuel expansion 3 Install fuel cap and let an...

Страница 18: ...ealant to seal the LPG hose connections Always position the cylinder so the connection between the valve and the regulator won t cause bends or kinks in the hose Spray a soapy water solution one part...

Страница 19: ...atio Other high altitude issues can include hard starting increased fuel consumption and spark plug fouling To alleviate high altitude issues other than the natural power loss FIRMAN can provide a hig...

Страница 20: ...any Use a ground fault circuit interrupter GFCI in any damp or highly conductive area such as metal decking or steel work DO NOT touch bare wires or receptacles DO NOT use generator with electrical co...

Страница 21: ...the weather Keep exhaust pipe clear of foreign objects Keep generator away from open flame Keep generator on a stable and level surface WARNING Surge Protection Voltage fluctuation may impair the prop...

Страница 22: ...un at no load for few minutes upon each initial start up to permit engine and generator to stablize StartingtheGenerator RecoilStart LPG 1 Before starting the generator check for loose or missing part...

Страница 23: ...EEN 6 Disconnect all electrical loads from the generator Never start or stop the generator with electrical devices plugged in or turned on 7 Move choke lever located on engine to START position NOTE D...

Страница 24: ...ctor switch is turned to the GAS position the indicator light will become RED up to 4 minutes before goes off Starting the engine successfully during these 4 minutes will turn the indicator light GREE...

Страница 25: ...g the engine successfully during these 4 minutes will turn the indicator light GREEN 6 Disconnect all electrical loads from the generator Never start or stop the generator with electrical devices plug...

Страница 26: ...do not exceed the maximum wattage rating of the generator when using one or more receptacles Also do not exceed the amperage rating of any one receptacle Do not apply heavy electrical load during bre...

Страница 27: ...STARTED DURING BATTERY POWER SAVING MODE UNLESS THE FUEL SELECTOR SWITCH IS TURNED TO THE OFF POSITION AND THEN TURNED BACK TO THE GAS OR LPG POSITION Unwanted Shutdown The generator cannot be started...

Страница 28: ...ufficient fuel flow to the engine This is not an indication of a problem with the generator but only a problem with the flow of gas from the LPG cylinder If generator performance seems to be deteriora...

Страница 29: ...hart above Notice Once a year you should clean or replace the spark plug and replace the air filter New spark plugs and clean air filter assure proper fuel air mixture and help your engine run better...

Страница 30: ...o cause skin cancer in certain laboratory animals Thoroughly wash exposed areas with soap and water a Drain oil by removing the drain plug and the oil filler cap while the engine is warm Change engine...

Страница 31: ...ank causing a fire resulting in death or serious injury and or property Contact with muffler area could cause burns resulting in serious injury WARNING A B A Spark plug B Spark plug cap c DO NOT touch...

Страница 32: ...and attach with the screws Spark arrester screen Flange Screw Battery Replacement 1 Remove the spark plug wire from spark plug 2 Remove the nut and bolt from the negative and positive posts 3 Loosen...

Страница 33: ...il it stops from lack of gasoline This will dry out all remaining gasoline in tank fuel lines and carburetor 5 Turn fuel selector switch to OFF position Fully close the LPG cylinder knob if it is open...

Страница 34: ...tic battery charging circuit The battery will receive charging voltage when the engine is running The battery will maintain a proper charge if the unit is used on a regular basis about once every two...

Страница 35: ...esh gasoline 7 Connect wire to spark plug 8 Replace spark plug 9 Drain gas tank and carburetor fill with fresh gasoline 10 Wait 5 minutes and re crank engine 11 Contact authorized service facility 12...

Страница 36: ...Page 33 PARTS DIAGRAM AND PART LIST H05753 PARTS DIAGRAM English Customer Service 1 844 FIRMAN1 142 143...

Страница 37: ...Page 34 439cc DUAL FUEL ENGINE PARTS DIAGRAM English Customer Service 1 844 FIRMAN1...

Страница 38: ...1 1 1 1 1 7 1 1 1 1 2 2 2 1 1 8 2 2 1 FIRMAN 439cc Dual Fuel Engine NO Part Number Qty Description 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104...

Страница 39: ...case Comp Bolt drain Washer drain Bolt Oil Level Sensor Flg Bolt M6 15 Bearing Locating Pins Bearing Balance Shaft Camshaft Comp Crankshaft Gear Crank Shaft Gear Drive Gskt Crankcase Cover Oil Dipstic...

Страница 40: ...by this warranty Normal Wear Your product needs periodic parts and service to perform well This warranty does not cover repair when normal use has exhausted the life of a part or the equipment as a w...

Страница 41: ...f God and other force majeure events beyond the manufacturer s control problems caused by parts that are not original FIRMAN parts units used for prime power in place of existing utility power where u...

Страница 42: ...failure under warranty of any warranted part MANUFACTURER S WARRANTY COVERAGE The exhaust and evaporative emissions control system on your is warranted for two years If any emissions related part on y...

Страница 43: ...ld Air cleaner 5 Crankcase breather assembly including Breather connection tube 6 Fuel tank evaporative emission control system including Purge valves Carbon canister Vapor hoses and fitting clamps FI...

Страница 44: ...P N 357745483 Rev 04 Firman Power Equipment Inc Peoria AZ 85381 www firmanpowerequipment com 8716 West Ludlow Dr Suite 6...

Отзывы: