11
NOTICE
: CONNECT THE
HTSS
IGNITER PARTS ACCORDING TO THE WIRING
DIAGRAM IN INSTRUCTION MANUAL.
NOTICE
: POWER AND GROUNDING SHOULD BE CONNECTED IN ACCORDANCE
WITH THE IGNITER WIRING DIAGRAM (SEE FIG. 3, 4 and 5), WITH PARTICULAR
ATTENTION TO THE CORRECT GROUNDING TO THE IONIZATION CIRCUIT AND TO
THE PLANT GROUNDING SYSTEM.
5.7 Mounting of the igniter in a retractor: the igniter's rod should be placed inside the guide pipe and fixed in the
retractor clamps. Mounting of the igniter in a retractor must be done so as to enable adjustment of the rod tip
position relative to the burner's/pilot’s nozzle. See retractor Instruction Manual and burner manufacturer
recommendations.
5.8 The guide tube should not be placed in the flame.
5.9 The power pack enclosure should be positioned as close to the burner as possible to reduce cable lengths, as
energy is lost with increasing cable length. The power pack must be in a location where the temperature does
not exceed its max. operating temperature. The box should be mounted with cable glands at the bottom, to
reduce moisture as well as dust and dirt ingress.
5.10
ATEX Certificate condition of safe use of igniter rods types HTSS-xxx-CEX and –J-CEX
:
the length of
the rod and the manner of its installation should ensure that the temperature of the outer surface of the
rod located in the hazardous area does not exceed 120°C.
5.11 Choose the correct glands depending on the hazardous zone rating. Mounting of ATEX glands should be
carried out in accordance with their mounting instructions. After installation, check
if
the gland is correctly
tightened.
5.12 The cable should be placed away from any hot elements to minimize the possibility of damage.
5.13 When installing in a hazardous area it is absolutely necessary to observe all ATEX regulations and
recommendations.
NOTICE
:
MAKE SURE TO CONSULT THE MANNER OF MOUNTING THE IGNITER
WITH THE PRODUCT MANUFACTURER/DISTRIBUTOR.
6. OPERATING INSTRUCTIONS
INDUSTRIAL HEALTH AND SAFETY ISSUES. STORAGE, HANDLING, TESTING:
6.1 The igniter, unless mounted on the burner, should be stored in a dry place, protected against mechanical
damage. Do not hit, step on igniter components.
6.2 The rod should be transported with care, avoiding impact against other objects or bending.
The rod should not be lifted by its ends to ensure no damage to rod, tip and connections.
6.3 Prior to starting the igniter it is necessary to check the condition of the cable and glands for mechanical
damage and make sure that the boxes (enclosures) are properly closed and glands are tightly fixed.
6.4 Powering the igniter's circuit should only be done after complete assembly of the rod, tip and only when
fitted in its operation-ready position at the burner. Check the proper insertion length L1 inside the gas
igniter as well as the position of igniter rod tip
against the gas nozzle - follow the gas pilot Manual.
6.5 Check the correct grounding of the igniter housings and circuit. Powering the rod outside a burner should
only be done to test its operation.