Note:

 Prior to the date code 0630, the 3K ohm resistor was supplied for external connection

from the Potentiometer Supply to terminal 6 the NX98 motor. From the date code 0630, the
resistor is supplied factory mounted between terminal 6 and the input to the feedback pot as
shown above.
If you are replacing an earlier version motor, remove the resistor which is located between
the 15v output in the control to terminal 6 in the NX98 motor.