SPECIFICATIONS (non CEX versions)

MECHANICAL:

Housing Material:

 

Cast aluminum with black polyester powder coat finish

Housing Weight:

4 lbs (2kg)

Environmental:

 NEMA 

4X, 

IP66

Hazardous Classifications:

 Class I, Division 2, Groups A, B, C & D, Class II, III, Division 2, 

 Groups F and G

 Ex II 3 G/D Ex nA IIC T4A

Mounting: 

Model 1000: 1" NPT female pipe mount with 3/4" NPT female
cooling air connection

Model 1000E: 1" BSP female pipe mount with 3/4" BSP female
cooling air connection

Model 1004: 1" NPT female pipe mount with 3/4" NPT female
cooling air connection

Model 1004E: 1" BSP female pipe mount with 3/4" BSP female
cooling air connection

Cooling / Purge Air Requirements

:

Source:

 Clean, 

dry, 

cool 

Volume:

 

4 SCFM (113 l/min) at 3/4" threaded mounting flange, or 1 inch “Y” 
fitting, mounted on scanner sight pipe. Temperature near the upper 
limit of the scanner operating range and/or use with dirty/dusty fuels
may require up to 15 SCFM (425 l/min).

Pressure:

 

Adequate to overcome furnace or windbox pressure

Temperature Rating:

 -40° F to + 150°F (-40°C to +65°C)

Humidity:

 0% to 95% relative humidity, non-condensing

ELECTRICAL:

Input Power: 

24 Vdc, + 20% / - 25%, 3.8 Watts

Electrical Connection:

Cable gland and 10 ft (3m) of captive cable

Relay Output

FLAME RELAY, (N.O.) / (N.C.) SPDT 

FAULT RELAY, (N.O.) SPST 

Contact Rating: 

Minimum: 1 mA @ 5 Vdc 

Maximum: 2 A @ 30 Vdc 

2 A @ 240 Vac 

Status Indication: 

Internal LED: “Flame Signal”, “Fault Indication”

Analog Output:

4-20 mA DC current, referenced to 24 Vdc common, maximum 
connected load 750 ohms

INTEGRAL CABLE SPECIFICATION:

Cable Specification:

P/N 59-536

Multi-core 8 conductor, color coded, #18 AWG wires and overall braided shield.
Nominal O.D. = .38” (9.6 mm)
RoHS Compliant

Cable Jacket:

 PVC 

jacket, 

Meets UL PLTC  Class 1, Div 2, no conduit required. 
UV resistant, Oil resistant.

Temperature Rating:

 -40 °C to 105 °C

CAUTION: Spring fasteners should be clipped and tightened to ensure a good bond to
housing and maintain the integrity of the NEMA 4X rating.

Содержание 65UV5-1000

Страница 1: ...ed to terminate the cable at the housing Note The 65UV5 1000 1000E scanners became obsolete in 2008 and were replaced by the enhanced capability of the 65UV5 1004 and 1004E scanners APPLICATION Fireye...

Страница 2: ...the ultraviolet tube While the shutter is open flame presence or absence is detected The self check shutter operation and fault diagnostics are fully described later in this bulletin SPECIFICATIONS FI...

Страница 3: ...se with dirty dusty fuels may require up to 15 SCFM 425 l min Pressure Adequate to overcome furnace or windbox pressure Temperature Rating 40 F to 150 F 40 C to 65 C Humidity 0 to 95 relative humidity...

Страница 4: ...ressure Temperature Rating 40 F to 150 F 40 C to 65 C maximum dependent on T classification Humidity 0 to 95 relative humidity non condensing ELECTRICAL Input Power 24 Vdc 20 25 supply current 100 mA...

Страница 5: ...ame too short or in the wrong position to ignite the main flame reliably thus prohibiting main fuel admission NOTE Reliable signals must be obtained at all air flows and furnace loads ranges of fuel f...

Страница 6: ...atisfied by continuous injection of purge air The scanner mounting may be made with provision for purge air through the 3 4 opening as shown in Figure 6 Item A or C or through a 1 tee wye connection a...

Страница 7: ...HT PIPE BY OTHERS ALTERNATE MOUNTING NOT ADJUSTABLE 60 1664 1 SWIVEL MOUNT 35 127 HEAT INSULATING NIPPLE 60 1199 1 NPT 60 1199 2 BSP SEALING COUPLING WITH QUARTZ WINDOW REQUIRED WHEN SCANNER LENS IS E...

Страница 8: ...N NOTE 4 FLAME OFF FLAME ON NOTE5 NOTE 6 FLAME STRENGTH EARTH GROUND EXTERNAL FUSE CABLE COLOR CODES AND DESCRIPTIONS BLUE Relay voltage input 5 VDC to 230 VAC 1 mA to 2000 mA fused BLACK Safety Relay...

Страница 9: ...The installer must use a suitable EX cable gland or conduit fitting at the CEX housing s NPT threaded cable entry opening To reduce electrical noise interference take precautions to keep the scanner...

Страница 10: ...sed can vary between 50 ms and 300 ms In the event of a self check failure the flame relay will de energize INDICATION LEDs The 65UV5 contains a color coded internal LED that indicates flame status an...

Страница 11: ...the ignition spark This is accomplished by cut ting off the fuel to the pilot and attempting to start the pilot using the spark igniter If the system responds to the spark the sighting should be real...

Страница 12: ...front is a plane within the combustion space separating the region of unburned fuel from the burning fuel Note There is an inverse relationship between discrimination and sensitivity Table 4 Heat Insu...

Страница 13: ...e tube can only be inserted into the socket with the electrodes broadside to the shutter window 4 Clean the quartz lens and tube with glass detergent or glass cleaning agents which contain no abrasive...

Страница 14: ...r Description 4 290 1 UV Tube 61 6974 Shutter Assembly 002608 001 Flange Gasket 002611 001 Scanner Lens 101537 001 Lens Retaining Ring 107427 006 Lens O Ring 2 required UV TUBE SHUTTER SECURING SCREWS...

Страница 15: ...127 1 NPT HEAT INSULATING NIPPLE 35 127 3 BSP HEAT INSULATING NIPPLE L 92 48 QUARTZ WINDOW for 61 1199 Sealing Coupling shown in Fig 15 A 60 1664 3 NPT SWIVEL MOUNT 60 1664 4 BSP SWIVEL MOUNT A B B 60...

Страница 16: ...s found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND F...

Отзывы: