31
TROUBLESHOOTING
The 45FS1/45UVFS1 flame scanner contains certain diagnostic information helpful in troubleshoot-
ing the scanner. In the event of a problem where you need to contact the factory, please perform the
following steps.
1.
Press the Program Enable key to enter Setpoints Menu.
2.
Press the Advance key
(
➡
)
until the Setpoint AIM is displayed.
3.
Press the Help key (?) and Change key (
▲
) simultaneously until the screen displays
X1 =
followed by a numeric value. Enter this value in the table below.
4.
Press the Change key (
▲
) until the screen displays:
X2 =
followed by a numeric value. Enter this value in the table below.
5.
Each time the Change key is pressed the values advance to the next diagnostic. There are a total
of 15 diagnostic values (X1 through XF). Enter all of the values in the table below.
NOTE: The value for XD will change.
6.
After the diagnostic XF appears, the screen again displays the setpoint AIM. Repeating steps 3
through 5 will display the diagnostics again.
DIAGNOSTIC VALUES – TO BE COMPLETED BEFORE CONTACTING THE FACTORY
FIGURE 22
REPLACEMENT PARTS
X1
X2
X3
X4
X5
X6
X7
X8
X9
XA
XB
XC
XD
XE
XF
Original equipment factory replacement parts are avail-
able at various sub-assembly levels. For example, in Fig-
ure 22, item B, the Glass Lens Assembly (61-2275-3)
contains three parts which can be purchased as a unit, or
separately.
A. 29-248
FLANGE GASKET
B. 61-2275-3
GLASS LENS ASSEMBLY FOR 45FS1
61-2275-4
QUARTZ LENS ASSEMBLY FOR 45UVFS1
C. 129-162-1
KIT, KEYPAD AND BEZEL FOR 45FS1 AND 61-6625 (NOT SHOWN)
129-162-2
KIT, KEYPAD AND BEZEL FOR 45UVFS1 AND 61-6694-1 (NOT SHOWN)
D. 129-169-1
KIT, WIRING COVER (SIDE COVER) AND GASKET FOR 45FS1 (NOT SHOWN)
129-169-2
KIT, WIRING COVER (SIDE COVER) AND GASKET FOR 45UVFS1 (NOT SHOWN)
A
B