7.8 WIRING TABLES
Fig.16:
WIRING TABLE FOR INITIATING CIRCUITS
WIRE GAUGE
MAXIMUM WIRING RUN TO LAST DEVICE (ELR)
(AWG)
ft
m
22
2990
910
20
4760
1450
18
7560
2300
16
12000
3600
14
19000
5800
12
30400
9200
NOTE : MAXIMUM LOOP RESISTANCE SHOULD NOT EXCEED 100 OHMS
Fig.17:
WIRING TABLE FOR Notification Circuits
TOTAL
MAXIMUM WIRING RUN TO LAST DEVICE (ELR)
MAX. LOOP
SIGNAL LOAD
RESISTANCE
18AWG
16AWG
14AWG
12AWG
Amperes
ft
m
ft
m
ft
m
ft
m
Ohms
0.06
2350
716
3750
1143
6000
1829
8500
2591
30
0.12
1180
360
1850
567
3000
915
4250
1296
15
0.30
470
143
750
229
1200
366
1900
579
6
0.60
235
71
375
114
600
183
850
259
3
0.90
156
47
250
76
400
122
570
174
2
1.20
118
36
185
56
300
91
425
129
1.5
1.50
94
29
150
46
240
73
343
105
1.2
1.70
78
24
125
38
200
61
285
87
1.0
RS-485 WIRING:
See the Connection Diagram.
4-WIRE SMOKE WIRING:
The maximum allowable current is 0.15 Amperes. The maximum allowed Voltage Drop
is 1 Volt. Refer to the Indicating Circuit Wiring Table above.