INSTALLATION AND MAINTENANCE GUIDE FOR 

 ELECTRIC FIRE PUMP CONTROLLERS 

MODEL SERIES: 

FTA740, FTA750, FTA1000, FTA1250, FTA1300,  

FTA1350, FTA1500, FTA1800, FTA1930 

 

Содержание FTA1000 Series

Страница 1: ...1 INSTALLATION AND MAINTENANCE GUIDE FOR MARKIII ELECTRIC FIRE PUMP CONTROLLERS MODEL SERIES FTA740 FTA750 FTA1000 FTA1250 FTA1300 FTA1350 FTA1500 FTA1800 FTA1930...

Страница 2: ...utomatically on low pressure detection by the pressure sensor when the pressure drops below the cut in threshold MANUAL START The motor can be started by pressing the START push button regardless of t...

Страница 3: ...en tested in accordance with the ICC ES AC156 IBC 2015 CBC 2016 OSHPD Special Seismic Certification Preapproval OSP and ASCE 7 10 Chapter 13 standards Proper installation anchoring and mounting is req...

Страница 4: ...ing has been provided Controllers must be installed inside a building and they are not designed for outside environment The paint color may change if the controller is exposed to ultraviolet rays for...

Страница 5: ...or full load current for FTA1250 model 6 wires plus ground sized at 125 of 58 of the motor full load current for FTA1300 and FTA1350 models Incoming Power Connections Incoming normal power is to be co...

Страница 6: ...ng label is the most important label It must be read carefully to ensure the compatibility between the controller and the installation Verify that the controller is installed securely on the wall or o...

Страница 7: ...he panel all in accordance with the specifications in order to minimize interference with other equipment Verify and or install the proper water connections for the water input and the drain They must...

Страница 8: ...on then put the circuit breaker disconnecting means in ON position Verify the readings on the controller main screen Once the controller has booted up the First Start Up page appears The controller wi...

Страница 9: ...2 L3 and L1 L3 nominal is the same as what is written on the fire pump controllers nameplate The fire pump controller will validate the nominal voltage automatically versus what it has been built for...

Страница 10: ...the motor is turning in the right direction by checking the Check on Normal Power selector box Once the motor rotation has been checked go back to the controller start up page and press the Verify pre...

Страница 11: ...r system specifications Cut Out value will default to Cut In plus 10 PSI To manually enter the cut out select the check box beside it and enter the desired value optional When finished press the Servi...

Страница 12: ...12 From the Home page verify that the displayed values are correct The First Start up is now completed The controller is fully installed and configured...

Страница 13: ...years of service the Mark III battery may become less efficient and could lose the time after a shutdown Alarm Buzzer The alarm buzzer is activated under default faulty conditions stated by the NFPA20...

Страница 14: ...seconds 4 Turn ON all disconnecting means Pressure Transducer Test The controller will test the pressure transducer at least once a week if no manual run test or no weekly test has been conducted Dur...

Страница 15: ...nd the set points Screen Saver After 5 minutes of inactivity on the Mark III the screen will dim it s brightness to 25 After 10 minutes of inactivity on the Mark III the Black Screen screen saver will...

Страница 16: ...rvice Statistics and Last Service Statistics pages Download This button leads to the Download page which allows the user to download information including the user manual drawings logs statistics and...

Страница 17: ...and Cut In can be set on this page It is possible to install a custom Service card on this page Contact Firetrol for more information Pressing on the question mark on the Mark III will redirect to th...

Страница 18: ...18 Firetrol Inc 1 919 460 5200 3412 Apex Peakway Apex NC 27502...