6.4. Exiting Alignment Mode.

 

 

Do not remove the detector from the wall during this action. 

 

Using the mode switch (See fig. 4) select ‘Operating Mode’ (Switch will be in the down position).  

 

On exiting ‘Alignment mode’ the Detector will perform an internal calibration check. If this fails, which would be 

due  to  bad  alignment  or  either  electrical  or  optical  noise,  the  power  level  will  try  to  compensate.  If,  after  60 

seconds, the power level is still not correct, the Fault LED will illuminate and the panel will show a Fault. In this 

case the alignment procedure must be repeated. 

 

If the internal calibration check completes satisfactory, the AMBER LED will flash once every 10 seconds. The 

panel will need to be reset. The Detector will be in normal operating mode. 

 

7. System Testing. 

 

After successful installation and alignment the System will require testing for both alarm and fault conditions. 

 

7.1. Alarm (smoke) Test.

 

 

Taking note of the threshold selected during installation (default 35%). 

 

Select obscuration mark on filter to correspond with the Detector alarm threshold (see fig. 3). 

 

Place the filter over the receiver optics (Top of Detector Head 

 opposite end to the status indication LED’s) at 

the correct obscuration value determined by the threshold selected, i.e. if a threshold of 35% has been selected 

position the filter just past the 35% obscuration value on the filter (see fig 3.). 

 

Take care not to cover the transmitter optics. 

 

The Detector will indicate a fire within 10 seconds. 

 

7.2. Fault Test.

 

 

Cover the Prism(s) totally with a non-reflective material and confirm that the Detector indicates a fault condition 

after  approximately  10  seconds.  The  Amber  LED  on  the  Detector  will  flash,  and  the  panel  will  show  a  Fault 

condition.  The  fault  condition  will  automatically  reset  after  a  period  not  greater  than  2  seconds  when  the 

obstruction is removed. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 3. 

 obscuration value 

Align filter for correct obscuration/threshold setting 

Transmitter Optics 

Receiver Optics 

Status Indication LED’s 

RED 

AMBER 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание FD2705R

Страница 1: ...tres Range 50 100 Metres Unique simple alignment Loop powered Selectable alarm thresholds Low current consumption Automatic contamination compensation 22318 26 01 Loop Powered Analogue Addressable www...

Страница 2: ...Detector monitors long term degradation of signal strength caused by component ageing or build up of dirt on optical surfaces This operates by comparing the received infrared signal against a standard...

Страница 3: ...n be increased from 7 5 metres either side of the beam to 7 5 7 5 x 20 100 metres 9 metres Therefore with a roof pitch of 20 degrees the lateral coverage can be increased from 7 5 metres either side o...

Страница 4: ...lls as these surfaces do and will move Determine the position of the Head Assembly which must be mounted on a solid structure between 0 3 and 0 6 metres below the ceiling and no closer than 0 5 metres...

Страница 5: ...nment Mode Do not remove the detector from the wall during this action Using the mode switch See fig 4 select Alignment Mode Move switch to the middle position At this time there will be a fault condi...

Страница 6: ...nd enter the Operating Mode LED flashing Slowly adjust a thumbwheel in one direction and observe the LED s LED flashing For optimum alignment deflection of the beam in all four planes should cause the...

Страница 7: ...te of the threshold selected during installation default 35 Select obscuration mark on filter to correspond with the Detector alarm threshold see fig 3 Place the filter over the receiver optics Top of...

Страница 8: ...n connector on the left is for future use 8 2 DIP Switch Settings Access to the configuration and address settings is through the back plate of the Detector Head See Fig 4 8 3 Typical Loop Wiring Fire...

Страница 9: ...22318 26 01 9 Detector Interface Assembly Configuration Settings SENSITIVITY X X X X X X X 2 X 1 3 4 B A A B Fig 4 www acornfiresecurity com www acornfiresecurity com...

Страница 10: ...00100101 19 10011000 62 01000110 105 10100101 20 00000100 63 11000110 106 01100101 21 10000100 64 00100110 107 11100101 22 01000100 65 10100110 108 00010101 23 11000100 66 01100110 109 10010101 24 001...

Страница 11: ...880nm Head Maximum Size Width 130mm Height 210mm Depth 120mm Weight 740 gm 12 Service Application Notes For full compliance with BS5839 part 5 use 25 and 35 default thresholds The threshold of 50 is r...