FPX103C Auto DUAL LOOP AUTO/MANUAL FIRE CONTROL PANEL 

 Iss 1.0 

SUMMARY: 

Dual detection loops with full fault monitoring.

Automatic extinguisher operation after shutdown.

“Double knock” automatic activation logic.

Automatic Engine/fuel/fan shutoff capability.

“Spindown” delay ensures extinguishant is not vented.

Extinguisher activation button with anti-tamper tag.

Universal 12 or 24Vdc electrical power.

Low power consumption in “PARKED” mode.

Full fault monitoring on all detector and firex circuits.

Supports up to 6 aerosol fire extinguisher/generators.

Very low false activation potential, tamper seal on ManOp

The unit is reverse polarity, transient and EMC protected.

Custom behavior logic available on request.

Shutdown  and delayed firex  activation  improves  effectiveness  and  saves  cost  of  extra  extinguishant. 
Most existing extinguishing systems release the agent into a high airflow environment which makes it 
almost  completely  ineffective.  Given  that  a  7  Liter  4  stroke  engine  at  3000RPM  (that’s  50revs/sec) 
aspirates 175 Liters or 0.175m

3

 of air 

per second

, add to this ventilation fan flow and the necessity for 

a shutdown with engine/fan spindown delay before activation is obvious. 

The FPX103C has effectively eliminated spurious activation warranty costs which are regularly caused 
by  the  inherent  characteristics  of  microprocessors,  semiconductor  power  switches  and  inquisitive 
fingers.  Our  tamper  evident  tag  technology  and  our  strict  electronic  design  rules  has  proven  highly 
effective.  To  eliminate  the  inherent  hazards  of  microprocessor  control  the  FPX103C  uses  a  fully 
parallel path programmable logic device, which is coded using a language called VHDL, commissioned 
by US DOD and used for high reliability and safety critical applications. 

FEATURES: 

2-wire Smoke, thermal or Linear Heat Sensors up to 50M are continuously monitored for alarms, open
circuit and chassis faults. LED flash codes indicate the location of an alarm or fault condition.
An internal alarm sounder and relay to drive a loud external audible alarm unit up to 2Amps.
Uncommitted relay change-over contacts are available for fuel shutoff, engine/fan shutdown.
The delay option provides a selectable spin-down time so that the extinguishant is not wasted.

“PARKED MODE” is entered when unit senses that ignition is turned off and provides automatic

extinguisher operation should both loops alarm - switching off engine during a double alarm will also
enter timed auto activation mode (aka driver “legging it” protection).
There is an electrical input for an override keyswitch to circumvent shutdown circuits for restarting.

FUNCTIONAL NOTES: 

Any loop alarm condition will operate audible and visual alarm indications as follows: 

Single loop alarm condition produces internal pulsed alarm (1 per sec) and fan shutdown.

Dual loop alarm condition produces internal pulsed alarm (2 per sec) and automatic
extinguisher and fuel solenoid operation after spindown delay (user set on dip switches),
audible alarm goes continuous.

Alarm LED flash code indicates which loop is in alarm (1=1blink, 2=2blinks, 1&2=3blinks).

The spindown delay allows time for fan and engine to stop before extinguisher is activated. This is to 
save extinguishing agent that would otherwise be wasted through venting.  The timer tracks the 

Содержание FPX103C

Страница 1: ...FPX103C Dual Loop Auto Manual Fire Control Panel Technical Manual...

Страница 2: ...oprocessor control the FPX103C uses a fully parallel path programmable logic device which is coded using a language called VHDL commissioned by US DOD and used for high reliability and safety critical...

Страница 3: ...lter time the unit will confirm activation request by flashing 2ALARM AUTO LED and internal beeper fan and fuel solenoid shutdown relays are activated immediately After spindown timeout the extinguish...

Страница 4: ...on threshold Approximately 20K Ohms End Of Line Resistor 10K Ohms Fault monitoring Open circuit or ground fault fault indication Alarm Output Relay Contacts 2A VinDC Vin thru NO relay circuit VFC Outp...

Страница 5: ...t must be located to prevent excessive moisture or water getting to the unit especially the rear connections Locate to avoid excessive direct solar exposure WARNING And some common sense Refer to the...

Страница 6: ...Outline Mounting drawing...

Страница 7: ......

Страница 8: ...Typical Application wiring Linear Heat Detector sensors...

Страница 9: ...g the intellectual property rights of others For Materials or Equipment manufactured by Third Parties and not by FirePro Systems the Buyer shall only be entitled to the benefit of any such warranty or...

Страница 10: ...FirePro Systems 6 Koumandarias Street PO Box 54080 CY 3720 Limassol Cyprus EU Tel 357 25 379999 Fax 357 25 354432 Email mail firepro com www firepro com...

Отзывы: