Kiwa
®
declaration
K94463/05
Page 5 of 6
FirePro Ignition device for Non-Pressurized Condensed Aerosol
Generators
Cross reference CEN/TR 15276-1, Fixed fire fighting systems - Condensed aerosol extinguishing systems -
Part 1: Requirements and test methods for components, February 2009
Chapter
Description
Demand
1)
Result
Remarks
4
Component requirements
4.4
Ignition device
4.4.2
Electrical ignition device
A
Pass
Standard electrical activator in
conjunction with thermal ignition
device, see 4.4.3
4.4.3
Thermal ignition device
A
Pass
Bi-metal switch, heat cable and
BTA ignition device (Bulb Thermal
Activator)
See 5.12.2, 5.12.3 and 7.15
See Kiwa declaration K90415 and
K97969
4.4.4
Other methods of ignition device
N/A
5.
Condensed aerosol generator requirements
5.12
Ignition device
5.12.2
Electrical ignition device
Standard electrical activator only
tested for function in conjunction
with the following ignition devices:
Bi-metal:
•
60 ºC
Heat cable:
•
68 ºC
See 5.12.3 and 7.15
The bi-metal switch and heat cable
are mandatory equipped with the
FPC-5 ignition device.
5.12.3
Thermal ignition device
A
Pass
Bi-metal switch:
•
60 ºC
Heat cable:
•
68 ºC
BTA ignition device (Bulb Thermal
Activator):
•
57 ºC (glass bulb)
Other bulb temperatures are
available.
See information, instruction
& user manual § 9.
The bi-metal switch and heat cable
are mandatory equipped with the
FPC-5 ignition device.
See 7.15
Содержание FPC-5V2