Fire Control Panel 

FP-C2 

Rev 7.0

 

 

 

 

Page  |  

6.

 

Connecting to Master Fire Panel 

 

General 

To  connect  to  a  Master  Indicator  Panel,  there  is  some  connections  to  be  made  between  the  panels  and  then  some 
programming configuration in the Master Panel. 

 

FPC-2 as a sub-panel with stand-alone detection and activation 

Following explains connection and configuration to Sigma XT 

Master  Panel.    The  concepts  will  be  similar  to  other 
brands/types on master panel. 
The  connections  are  24vDC  power  which  can  come  from 

Sigma XT 

 or an appropriate external source, and a Single 

detection Zone is require on Sigma to allow inputs from FPC-
2. 
The EOL Resistor ensures that this circuit is monitored from 
the Sigma XT panel. 
Once  the  connections  are  complete.    The  Sigma  XT  panel 
must  be  programmed  correctly  to  set  up  the  FP-C2  as  a 

remote device.  This must be done so that FP-C2 is not treated 
as a regular detection device.  When programmed correctly, 

the FP-C2 will alert the main Sigma XT panel of any alarm or 
fault states. 
On the Sigma XT FIP, enter Access Level 2 by turning the key in 

“Enable  Control”  port  on  the  Detection  ca

rd  (top  card)  or  by 

releasing the read switch by opening the inner Perspex door. 

1.

 

Move the “Write Enable” switch to the right 

on the 

Detection Card (top card).  The “System Mode” LCD 
display will read “00”.

  

2.

 

The FIP’s detection 

options are numbered.  Using the 

controls on the Detection Card, navigate the “System 
Mode” LCD display reads “7#”.  To do this press the 
“Mode (+10)” button until the first number is “7” and 
then press the “Select (+1)” button until the display shows the correct detection circuit.

 

3.

 

The detection circuit number will have a flashing dot next to the 
number, indicating that it is programmed for conventional detection.  

Press the “Enter” button to change the detection circuit to S/C mode.  

This will cause the flashing dot to turn off.  

4.

 

Mo

ving the “Write Enable” switch to the left

 

Thermal Fuse Connection 

A Thermal Fuse to be connected to the ONE of the FirePro Aerosol 
Generators in the activation circuit. 
The Thermal Fuse allows notification to a control panel that a FirePro 
unit has activated.   It should be installed in accordance with the 
instructions included in the relevant FirePro document. 

Menu setting in the XT card allows for a 

normally closed (inverted) 

input to be used. 

 

 

 

Connect Thermal Fuse to 

Rel.P Switch on Sigmat XT Panel 

Содержание FPC-2

Страница 1: ...Maintenance Manual Table of Contents 1 Introduction 2 2 Operation 2 3 Panel Operation 2 4 Installation and Mounting 3 5 Installation of FirePro Generators 5 6 Connecting to Master Fire Panel 6 7 Maint...

Страница 2: ...r heat detection cable or smoke detector the red Fire indicator will be lit the FirePro Aerosol Generators will operate and immediately discharge extinguishing Aerosol into the protected area the inte...

Страница 3: ...erminals along the top of the circuit board Cabling must comply with the Australian Standards The resistance of any cable must not exceed 25 ohms Terminals are capable of accepting wires of up to 2 5m...

Страница 4: ...or other device Cabling Requirements Cable Requirements All cabling in the FirePro Installation MUST be done using 0 75mm shielded Fire Rated Cable Care taken to ensure that all cables are isolated a...

Страница 5: ...t rescue of any trapped personnel shall be provided including Adequate aisle ways routes of exit Alarms audible and visual that operate immediately on detection of the fire Signs in accordance with re...

Страница 6: ...Control port on the Detection card top card or by releasing the read switch by opening the inner Perspex door 1 Move the Write Enable switch to the right on the Detection Card top card The System Mod...

Страница 7: ...will require connection back to the master panel To make the FPC 2 compatible with an addressable input module move jumpers J1 and J2 from their default positions position A to position B The FIRE NO...

Страница 8: ...e fuse will blow on EACH test Note If the system has been activated the system activation fuse needs to be inspected as blown fuse will show as a fault The Fuse is 1 6AMP Quick Blow 9 Specifications M...

Отзывы: