10
Specification
Dimensions (W/H/D)
73/130/35 mm
Weight
220 g. including batteries
Operating Temperature Range
0 °C – +60 °C (32 °F – 140 °F)
Relative Humidity Range
10% – 93% non-condensing
Operating Voltage
6V
(supplied by 4 AA alkaline batteries such as Duracell or equivalent)
Battery Operating Time
2 – 3 years, dependant on battery
and environmental conditions
Average Current Consumption:
Standby: 70µA/Alarm: 3.0mA
Activation Pulse (good battery)
0.9A/4 seconds
Activation temperature – Fixed Temperature
80 °C
Activation temperature – Rate of Rise
8 °C/minute, if over 40 °C
or Fixed Temperature
80 °C
Remote Activation resistance to trigger alarm
150 – 600 Ohm
Remote Activation End of Line Resistor
5.1 K Ohm
Max current draw from open collector output
50mA
All values are nominal. Specifications are subject to change without prior notice.