Page 6 of 6 
 

 

10 

Specification 

 

Dimensions (W/H/D) 

 

 

 

 

73/130/35 mm 

Weight 

 

 

 

 

 

 

220 g. including batteries 

Operating Temperature Range   

 

 

0 °C – +60 °C (32 °F – 140 °F) 

Relative Humidity Range   

 

 

 

10% – 93% non-condensing 

Operating Voltage   

 

 

 

 

6V 

(supplied by 4 AA alkaline batteries such as Duracell or equivalent) 
Battery Operating Time 

2 – 3 years, dependant on battery 

and environmental conditions 

Average Current Consumption:  

 

 

Standby: 70µA/Alarm: 3.0mA 

Activation Pulse (good battery)  

 

 

0.9A/4 seconds 

Activation temperature – Fixed Temperature  

80 °C 

Activation temperature – Rate of Rise  

 

8 °C/minute, if over 40 °C 

or Fixed Temperature 

 

 

 

 

80 °C 

Remote Activation resistance to trigger alarm 

150 – 600 Ohm 

Remote Activation End of Line Resistor 

 

5.1 K Ohm 

Max current draw from open collector output 

50mA 

 