Guidelines about the wiring connections to the FirePro Aerosol Generators
FP-20SE/T/TH, FP-40S/T, FP-80S/T,FP-100S, FP-200S,FP-500S.
Step 1:
Open the package and take one Aerosol Generator unit.
Step 2:
Disconnect the moving parts of the aerosol generator and separate the 3 units.
Unit 1: Cable gland fixing component.
Unit 2: Cable gland & Activator cable housing.
Unit 3: Generator.
Step 3:
Prepare the cable / wires with the correct size.
“This is very important” please be sure that you follow correctly the below step by
step procedure:
Step 3.1:
Mark the cable 6.5 cm from the edge. Point (A).
Step 3.2:
Mark 3 cm from point (A) to point (B). Remove the shield of the cable from
point (B) to the edge of the cable.
Step 3.3:
Cut the positive wire ( + ) and negative wire ( - ) 1.5 cm from
point (B) to point (C).
Step 3.4:
Clean the edges of the positive wire ( + ) and negative wire ( - )
4mm approximately. From point (C) to point (D).
Step 3.5:
Slice the shield of the cable from point (B) to point (A).
Step 3.6:
Take out the earth wire.
Step 3.7:
Cable is ready to be used.
Step 4:
Pass the prepared cable through the
UNIT 1
(Cable gland fixing component) and
through the
UNIT 2
(Cable gland & Activator cable housing).
DO NOT PASS THE EARTH WIRE.
Step 5:
Connect the cable wires, positive ( + ) & negative ( - ), with the aerosol unit connector
with any of the 2 non polarized activator cables.
Step 6:
Pull back the cable until the edge of the cable shield just shown.
Step 7:
Hold the cable avoiding the turning of the connector within housing while turning by
hand the activator cable housing (part 1) with activator cable housing (part 2).
Step 8:
Put silicon within the gland around cable in order to seal it.
Step 9:
By using two spanner keys connect Unit 1 (cable gland fixing component) with Unit 2
(Cable gland & Activator cable).
Step 10:
Connect earth wire with earth tag.
Step 11:
Seal with silicone the cut shielded cable and the entrance of the cable into the Unit
1 (cable gland fixing component).