Installation, Wiring 
and Earthing 
Guidelines

 

for Cylindrical Aerosol units

Version 2, 24-06-2016

Содержание FP-100S

Страница 1: ...Installation Wiring and Earthing Guidelines for Cylindrical Aerosol units Version 2 24 06 2016 ...

Страница 2: ...rosol Generator the Ring Bracket Step 2 Take L bracket and place it inside the Ring bracket Step 3 Align L bracket holes to the Ring bracket holes Step 4 Pass the screws through the aligned holes and tide them with the spanner key 11 13 to the nuts Use screw size M8 for the longer hole and screw size M6 for the smaller hole Step 5 Select type of screws suitable to the surface material to be fixed ...

Страница 3: ...o Front View Side View Bottom View Step 5 The aerosol generator is ready for cable connections Step 4 Pass the screws through the aligned holes and fix them on the surface material Step 3 Select type of screws suitable to the surface material to be fixed these screws are not supplied with the kit Step 2 Align Bracket holes with surface material holes Step 1 Take the Bracket and place it on the aer...

Страница 4: ...ge 3 50mm Diameter U Type Metal Bracket Step 5 The aerosol generator is ready for cable connections Step 4 Pass the screws through the aligned holes and fix them on the surface material Step 3 Select type of screws suitable to the surface material to be fixed these screws are not supplied with the kit Step 2 Align Bracket holes with surface material holes Step 1 Take the Bracket and place it on th...

Страница 5: ...1 Take the Bracket part 1 and place it on top of the aerosol generator Step 6 The aerosol generator is ready for cable connections Step 5 Pass the screws through the aligned holes and fix them on the surface material Step 4 Select type of screws suitable to the surface material to be fixed these screws are not supplied with the kit Step 3 Align Bracket part 1 holes with Bracket part 2 holes Step 2...

Страница 6: ...fix them on the surface material Page 5 Step 5 Select type of screws suitable to the surface material to be fixed these screws are not supplied with the kit Step 4 Pass the screws through the aligned holes and tide them with the spanner key 11 13 to the nuts Use screw size M8 for the longer hole and screw size M6 for the smaller hole Step 2 Take L bracket and place it inside the Ring bracket Step ...

Страница 7: ...BY DATE DESCRIPTION D C B A 4 3 2 1 D C B A 4 3 2 1 Aerosol Generator FP 500S 1 0 Generator Installation guide line 24 06 2016 Michaelides Loucas Step 1 Pass through the Aerosol Generator the 2 Ring Brackets FirePro Page 6 ...

Страница 8: ... 2 1 D C B A 4 3 2 1 Aerosol Generator FP 500S 1 0 Generator Installation guide line 24 06 2016 Michaelides Loucas Step 2 Take each L bracket and place it inside the Ring bracket FirePro Step 3 Align each L bracket holes to the Ring bracket holes Page 7 ...

Страница 9: ... Generator FP 500S 1 0 Generator Installation guide line 24 06 2016 Michaelides Loucas FirePro Step 4 Pass the screws through the aligned holes and tide them with the spanner key 11 13 to the nuts Use screw size M8 for the longer hole and screw size M6 for the smaller hole Page 8 ...

Страница 10: ...4 3 2 1 D C B A 4 3 2 1 Aerosol Generator FP 500S 1 0 Generator Installation guide line 24 06 2016 Michaelides Loucas FirePro Step 5 Select type of screws suitable to the surface material to be fixed these screws are not supplied with the kit Page 9 ...

Страница 11: ...2 1 Aerosol Generator FP 500S 1 0 Generator Installation guide line 24 06 2016 Michaelides Loucas FirePro Step 7 The aerosol generator is ready for cable connections Step 6 Pass the selected screws through the L bracket holes and fix them on the surface material Page 10 ...

Страница 12: ...ly From point C to point D Step 3 5 Slice the shield of the cable from point B to point A Step 3 6 Take out the earth wire Step 3 7 Cable is ready to be used Step 4 Pass the prepared cable through the UNIT 1 Cable gland fixing component and through the UNIT 2 Cable gland Activator cable housing DO NOT PASS THE EARTH WIRE Step 5 Connect the cable wires positive negative with the aerosol unit connec...

Страница 13: ...1 D C B A 4 3 2 1 FirePro FirePro Step 1 Open the package and take one Aerosol Generator Unit Step 2 Disconnect the Aerosol generator separate the 3 units Step 3 Prepare the cable Cable gland fixing component UNIT 1 Cable gland activator cable housing UNIT 2 Generator UNIT 3 3 cm 1 5 cm 6 5 cm 4 mm 2 X 1mm Earthing wire Cut the cable and take out the earthing wire Page 2 ...

Страница 14: ...ble from point B to the edge of the cable A A B 1 5 cm A B C Step 3 3 Cut the positive wire and negative wire 1 5 cm from point B to point C A B C Step 3 4 Clean the positive wire and negative wire 4mm approximately From point C to point D 4 mm D A B C Step 3 5 Slice the shield of the cable from point B to point A D 4 mm A B C Step 3 6 Take out the earthing wire D Step 3 7 Cable is ready to be use...

Страница 15: ...e 2 non polarized activator cables Step 6 Pull back the cable Activator cable housing PART 1 Activator cable housing PART 2 Connector Connector FirePro FirePro Pull back the cable until the edge of the cable shield just shown 1 0 Cable connection guide line 24 06 2016 Michaelides Loucas Cable gland fixing component UNIT 1 Cable gland activator cable housing UNIT 2 FirePro Page 4 Activator cables A...

Страница 16: ...nnect Unit 1 cable gland fixing component with Unit 2 Cable gland activator cable FirePro FirePro Activator cable housing PART 1 Activator cable housing PART 2 Hold the cable Put Silicone FirePro Cable Put Silicone Spanner key 22 1 0 Cable connection guide line 24 06 2016 Michaelides Loucas Cable gland fixing component TOP VIEW Cable gland fixing component UNIT 1 Cable gland activator cable housin...

Страница 17: ...ilicone the cut shielded cable and the entrance of the cable into the Unit 1 cable gland fixing component FirePro FirePro Earthing tag Silicone 1 0 Cable connection guide line 24 06 2016 Michaelides Loucas Silicone Cable gland fixing component UNIT 1 Page 6 Earthing wire Earthing wire FP 20SE T TH FP 40S T FP 80S T FP 100S FP 200S FP 500S ...

Страница 18: ...B A 4 3 2 1 DETAIL CABLE X24 Earthing wire Earthing wire Earthing tag Activator Cable Housing Part 2 Activator Cable Housing Part 1 Thermoconector Part 1 Cable connector Nikel plated M16 cable gland 2 X 1mm earthing wire 1 0 Cable connection guide line 24 06 2016 Michaelides Loucas Page 7 FP 20SE T TH FP 40S T FP 80S T FP 100S FP 200S FP 500S ...

Страница 19: ...FirePro Systems 6 Koumandarias Street PO Box 54080 CY 3720 Limassol Cyprus EU Tel 357 25 379999 Fax 357 25 354432 Email mail firepro com www firepro com ...