background image

OGF - RT Series

CLEARANCE TO COMBUSTIBLE DECORATIVE SURROUNDS

     Decorative surrounds i.e. timber

mantelpieces/combustible moulding must be

50mm (min) clear of the face side edges and top

face edge of the firebox.

     Upright legs and breast sections of

combustible surrounds must not project further

than 50mm (max) forward of the face of the firebox.

     Mantle shelves must be 300mm (min)

clear above the top edge of the firebox and must

not project more than 250mm (max) forward of

the face of the firebox.

     A non-combustible floor protector

(forehearth) at the base directly in front of the

firebox opening must be a minimum of 6mm

thick, project a minimum 300mm forward and

200mm on each side of the firebox opening.

MANTLEPIECE BREAST

GE

L

05

NI

M

50

MIN

50

MAX

250

MAX

00

3

NI

M

FIREFOX

OGF UNIT

4

Отзывы: