Battery pack replacement procedure

Caution: 

Do not open or attempt to replace the battery pack in a 

hazardous environment.

1. Loosen the two 4-40 set screws in the rear cover using a .050 Allen 

wrench (hex key).

2. Remove the rear cover. Note: Be careful not to get the anti-seize 

compound on hands and clothes.

3. Carefully remove the battery pack plug from the control board 

connector. The battery pack plugs into the left connector on the 

control board when the pistol grip handle is pointing downward.

4. Remove the battery pack.
5. Insert the battery pack replacement into the battery pack holder. 

Insure the battery pack is fully seated in the holder.

6. Plug the battery pack into the open connector on the left side of 

the control board J1.

7. Securely attach the rear cover by tightening five to six turns 

(minimum). Re-tighten the two set screws.

8. Charge the battery pack per the first paragraph within the 

operating instructions of this manual.

Optional equipment

Firefly Part No

Description

70719

Charger adapter plug

70718                          

Battery pack

Vibro-Meter  Inc

144 Harvey Road

Londonderry NH 03053

USA

Tel: +1 603 669 0940

+1 800 842 4291

Fax: +1 603 669 0931

[email protected]

www.vibro-meter.com

www.meggitt.com

ISO 9001 certified

Publication No 1031189, Rev F

Product disposal

This product may contain hazardous and/or toxic substances.  EU

member states shall dispose according to WEEE regulations.  All other

countries or states, please dispose of in accordance with existing

federal, state and local environmental control regulations

.

6 Plug the battery pack into the open connector on the

left side of the control board J1.

7 Securely attach the rear cover by tightening five to six

turns (minimum).  Re-tighten the two set screws.

8 Charge the battery pack per the first paragraph within

the operating instructions of this manual.

Optional equipment

Optional equipment

Optional equipment

Optional equipment

Optional equipment

VMI Part No

VMI Part No

VMI Part No

VMI Part No

VMI Part No

Description

Description

Description

Description

Description

70719

Charger adapter plug

70718

Battery pack

70822

UV attenuator assembly

Omniguard model 540 UV/IR test source

Omniguard model 540 UV/IR test source

Omniguard model 540 UV/IR test source

Omniguard model 540 UV/IR test source

Omniguard model 540 UV/IR test source

Operating and service manual

Vibro-Meter  Inc

144 Harvey Road

Londonderry NH 03053

USA

Tel: +1 603 669 0940

+1 800 842 4291

Fax: +1 603 669 0931

[email protected]

www.vibro-meter.com

www.meggitt.com

ISO 9001 certified

Publication No 1031189, Rev F

Product disposal

This product may contain hazardous and/or toxic substances.  EU

member states shall dispose according to WEEE regulations.  All other

countries or states, please dispose of in accordance with existing

federal, state and local environmental control regulations

.

6 Plug the battery pack into the open connector on the

left side of the control board J1.

7 Securely attach the rear cover by tightening five to six

turns (minimum).  Re-tighten the two set screws.

8 Charge the battery pack per the first paragraph within

the operating instructions of this manual.

Optional equipment

Optional equipment

Optional equipment

Optional equipment

Optional equipment

VMI Part No

VMI Part No

VMI Part No

VMI Part No

VMI Part No

Description

Description

Description

Description

Description

70719

Charger adapter plug

70718

Battery pack

70822

UV attenuator assembly

Omniguard model 540 UV/IR test source

Omniguard model 540 UV/IR test source

Omniguard model 540 UV/IR test source

Omniguard model 540 UV/IR test source

Omniguard model 540 UV/IR test source

Operating and service manual

Отзывы: