FireFlex TOTALPAC 2 PAR-3 Скачать руководство пользователя страница 8

 

Page 8 of 10

 

 

T

OTAL

P

AC

2 Integrated Fire Protection System 

PAR-3 Control Panel 

 

 

FM-072G-0-05 C 

 

 

9.  BATTERIES TECHNICAL DATA: 

Batteries are sealed construction, lead-acid rechargeable 
that allow a trouble-free, safe operation in any position.  
There is no need to add electrolyte as gases generated 
during overcharge are recombined in a unique "Oxygen 
Cycle". 
No special handling precautions or shipping containers – 
surface or air – are required due to the leak-proof 
construction.  
Under normal operating conditions four two five years of 
dependable service can be expected in stand-by 

applications or between 200 and 1000 charge/discharge 
cycles depending upon depth of discharge. 
The capacity of the batteries is expressed in amperes-hours 
(AH) and is the total amount of electrical energy available 
from a fully charged cell.  The standard batteries provided 
with the 

T

OTAL

P

AC

2

 unit is 7AH capacity and should provide 

enough power to provide the 5 minutes of alarm after 24 
hours on stand-by required by UL and C-UL.  12AH batteries 
are also available on option for the 90 Hrs standby period 
requested by Factory Mutual (FM).  The calculation chart 
below shall be used to confirm batteries will be adequate.

 

.1  Standby Battery Requirements 

The Standby Battery Current figure obtained in this table represents the amount of current that must be supplied by the 
secondary power source (batteries) to sustain the control panel operation for one hour. 

Control Panel (including a 

4XZM Relay module

) ..............................................................  

with AC power lamp OFF, System trouble lamp and audible signal ON

 

.096 

If using an extra 

4XZM Relay module

 ...............................................................  add .008 

 

If using a 

4XLM / RZA-4X Driver / Annunciator

 combination .............................  add .019 

 

Number 

in use 

Device current 

(see Device 

Compatibility Document 

for data)

 

Total 

current

 

Two-wire smoke detectors heads 

 X 

=   

Four-wire smoke detectors heads 

 X 

=   

End-of-line relays 

 X 

 

=   

Add 

Total current

 from the three lines above

ª

 

If using 

24Vdc RMS-Regulated Source

 (TBA-28/29) ............................  add load current 

 

Total Standby Battery Current

 

 

Amps

 

.2  Standby Period Required:

                     

Total Standby 

Battery Current

Standby Time 

(enter 24 or 90 hours 

of operation)

 

 

amps

   X 

hours

Place result here for 

Standby AH

ª

 

 

AH

 

3. 

 

Alarm 

Battery 

Requirements 

        

 

Alarm AH 

(enter 

0.25

 for 

5 minutes

 in alarm, or 

0.5

 for 

10 minutes

 in alarm) 

 

AH

 

4. 

 

Total 

Ampere-Hour 

Calculations 

       

 

Total AH needed 

(add 

Standby AH

 & 

Alarm AH then multiply by 1.2 de-rating factor

)

 

 

AH

 

Select a battery with equal or greater 

AH rating

 than the 

Total AH

 obtained above.  Batteries must be lead-acid type. 

Notes: 

1) 

Alarm AH

 assumes a maximum system draw of 3 amps in alarm for 5 minutes (0.25 AH) or for 10 minutes (0.5 AH). 

2) NFPA 

72-1993 

Local Fire Alarm Systems

 standard requires 24 hours of standby power. 

3)  Factory Mutual Systems require 90 hours of standby power. 
4)  The battery charger in this panel will charge a maximum of 18 AH of batteries within 48 hours (7 AH minimum). 
 

Содержание TOTALPAC 2 PAR-3

Страница 1: ...fore making any change In fire conditions when an initiating device circuit or predetermined combination of circuits is energized the panel activates the release and signaling circuits according to the Function Selector setting On the panel s display board the appropriate Alarm Trouble and Supervisory LED s will flash until the event has been acknowledged After depressing the Tone or Alarm Silence...

Страница 2: ... A second trouble will resound the buzzer Switch 3 Alarm Activate The Alarm Activate switch may be used to activate signaling circuits and relays Switch 4 System reset The Reset switch clears any activated output circuit If alarm or trouble conditions exist when the reset switch is pushed they will re activate the panel Front Panel Zone Status LEDs When the panel is activated zone status LEDs illu...

Страница 3: ... PAR 3 Control Panel Refer to Device Compatibility Document on our Web site and appropriate Fire Protection Equipment Approval Guides 4 Wire all alarm initiating devices sequentially for proper supervision 5 Pull required conductors and drill knockouts as required Note The control panel motherboard is factory pre wired and programmed for the configuration selected at the time of purchase All field...

Страница 4: ...ush door handle Figure 2 Typical Control Equipment Layout FM 072Q 0 19 C dwg NOTE Front door assembly not shown for clarity Spare Sprinkler Heads Storage Rack 12 heads capacity TBA Field Wiring Terminals Strip TBC TBR also when provided Typical Control Panel Motherboard Placement TBB Field Wiring Terminal Strip for 120 220 Vac Power Feed under protective cover Air Compressor Isolating Switch rated...

Страница 5: ...ads Storage Rack 12 heads capacity TBA TBC TBR Field Wiring Terminals Strip PAR 3 Control Panel Motherboard Placement Emergency Batteries BATT EARTH MICRO FAIL DIP Switches for System Programming J9 Troubleshooting LEDs 3 Placement of optional Status Annunciator Module MEA or Fail Safe Timer Elevators J9 Battery connector AC Circuit Breaker OPT 1 OPT 2 Refer to labels description for detail FM 072...

Страница 6: ...quire RESET to clear ALARM SILENCE Acknowledge for alarms and supervisories The ALARM SILENCE switch will silence the local piezo change any flashing alarm LEDs to steady and turn off the notification appliance circuits not the Releasing Circuits The ALARM SILENCED LED will illuminate Alarm silence is a latching function and requires a RESET to clear ALARM ACTIVATE The ALARM ACTIVATE switch may be...

Страница 7: ...he button identified ALARM SILENCE To select the previous zone press the button identified ALARM ACTIVATE a When selection of the disabled zones is completed release the button identified TONE SILENCE b The yellow lamp identified SYSTEM TROUBLE will flash Silence the audible signal by pressing the button identified TONE SILENCE 3 To reactivate the zones previously disabled repeat the procedure to ...

Страница 8: ...that must be supplied by the secondary power source batteries to sustain the control panel operation for one hour Control Panel including a 4XZM Relay module with AC power lamp OFF System trouble lamp and audible signal ON 096 If using an extra 4XZM Relay module add 008 If using a 4XLM RZA 4X Driver Annunciator combination add 019 Number in use Device current see Device Compatibility Document for ...

Страница 9: ...than 85 of rated voltage allow them to charge for 48 hours 3 If problem persists replace batteries Ground fault trouble Earth yellow LED ON 1 Remove field wiring from TBA Install dummy ELR 4 7K for 24V 2 2K for 12V 2 Remove both battery leads 3 If trouble clears connect one circuit at the time to pinpoint the problem 4 If trouble does not clear replace circuit board System Trouble LED ON Power tro...

Страница 10: ...Page 10 of 10 TOTALPAC2 Integrated Fire Protection System PAR 3 Control Panel FM 072G 0 05 C ...

Отзывы: