T
OTAL
P
AC
®
3
F
IRE
C
YCLE
®
III
Page 3 of 8
Integrated Fire Protection System
B
Mechanical Section - Deluge System - F
IRE
C
YCLE
®
III Release
FM-076A-0-52A
1.4.4 Manual operation
Anytime the handle of the manual emergency release
valve
(B10)
is triggered, pressure is released from the
priming chamber of the flow control valve
(A1)
causing
flow control valve to open. Water will flow into the system
piping network and alarm devices
(C1
and optional
C2)
will
operate
.
Water will flow from all open sprinklers/spray
nozzle on the system piping network. The PORV
(B9)
will
keep the flow control valve
(A1)
open.
1.4.5 Fail-safe condition
In case of AC power loss following a cycling discharge
stop, if the main water supply valve
(D1)
is still open while
the batteries have reached their cycle end, the normally
open solenoid valve
(F2)
will be de-energized, causing the
flow control valve
(A1)
to reopen with the help of the
PORV
(B9)
.
1.5 Emergency instructions
To take system out of service
WARNING !
Placing a control valve or detection system out
of service may eliminate the fire protection capabilities of
the system. Prior to proceeding, notify all local
AUTHORITIES HAVING JURISDICTION
. Consideration should
be given to employ a fire patrol in the affected areas.
After a fire, verify that the fire is OUT and that placing the
system out of service has been authorized by the
appropriate local
AUTHORITY HAVING JURISDICTION
.
Sprinklers piping that have been subjected to a fire must
be returned to service as soon as possible. The entire
system must be inspected for damage, and repaired or
replaced as necessary.
1.
CLOSE
main water supply valve
(D1)
.
2.
OPEN
main drain valve
(D3)
.
3. If applicable, silence audible devices (see section
E
CONTROLS
).
Note:
Electric alarms controlled by a pressure switch
installed at the ¾"-NPT (20mm) connection
(C2)
for a non-
interruptible alarm signal cannot be shut-off until the flow
control valve
(A1)
is reset or taken out of service.
4.
OPEN
flow test valve
(B6)
.
5.
CLOSE
priming valve
(B1)
.
6. Replace any detector that have been damaged.
7. Replace any automatic sprinkler that have opened,
been damaged or exposed to fire conditions.
8. Return the system to service as soon as possible (see
paragraph 1.6
PLACING THE SYSTEM BACK IN SERVICE
AFTER OPERATION
of the current section).
9. Perform all recommended maintenance procedures
(see paragraph 1.8
MAINTENANCE
in the current section).
Note:
When a system has been removed from service and
is subject to freezing or will be out of service for an
extended period of time, all water must be removed from
the priming chamber, trim piping, water supply piping and
any other trapped areas.