TESTING 

(

see 

IMAGE: 1

)

 

To test the RF transmission from the mounted position you can either generate a tamper by removing the cover or 
press the learn button located next to the tamper switch. Press and release ONCE to send a Smoke signal or press 
and HOLD for 2 seconds to send a Carbon signal.  To test the audio detection, press  and hold the smoke detector 
test button. Some Panels offer a Fire with Verification zone type. If this is the zone type programmed, you must press 
and hold the smoke detector button for at least 30 seconds to ensure that FireFighter™ has had sufficient time to 
identify the smoke alarm pattern and lock into alarm. Ensure the FireFighter™ cover is on and that you wear hearing 
protection.   

      

NOTE:  

This system must be checked by a qualified technician at least once every three (3) years.  Please test the unit once 

per week to ensure proper functionality.

 

 

Older NON temporal 3 Smoke Detectors 

If you happen to have an older NON temporal 3 pattern smoke detector you can change the Firefighter to be a 
universal listening device. When put into a universal listening pattern you must ensure that the Firefighter is not 
within listening distance of ANY Security alarm sirens or Alarm keypads. 
1.

 

Open the case, Remove the battery. 

2.

 

While holding the tamper switch IN, replace the battery, then release the tamper switch. 
This will toggle between Temporal and generic mode 
ONE flash:  Temporal 3 and 4 mode (Will only trigger on Temporal Patterns)  
TWO flashes: Generic listening mode. (Will trigger after 30 seconds of continuous 3K frequency sounder)  
You can always verify the mode by simply removing the battery and replacing it. The LED will flash once or 
twice depending on the mode it is in.  

3.

 

When in generic, 

non

-temporal 3 mode, the firefighter should not be installed in the same room as ANY alarm 

keypads or sirens. It is best to set the alarm off and make sure the RED LED on the firefighter does not hear any 
keypad or siren since it is looking for 30 seconds of continuous pattern at 3000-4000 Khz. If it does move the 
firefighter so it does not hear any siren or keypad that may be in the same room as the firefighter.  

WARNING: 

While the audio detector monitors its own battery, it does not monitor the battery in the smoke 

detectors. Batteries should be changed as per the original smoke detector manufacturer’s instructions. Always test 
the audio  detector and smoke alarms after battery installation to confirm proper operation

 

 
 
 
 
 
       LEARN BUTTON 

                                                                                                                                                                                                                                                                                    6” MAX

 

 

 
 

     TAMPER SWITCH

 

 
 

      MARKINGS TO LINE

 

      UP WITH EXISTING SMOKE  DETECTOR

 

 

BATT

 

 
 

   IMAGE 1

: ENROLLING / TEST / TAMPER BUTTON

 

  

IMAGE 2

: INSTALLATION DISTANCE

 

  

IMAGE 3

: SIDE MARKINGS

 

WARRANTY

 

Encore Controls  warrants that for a period of 2 years from the date of purchase that this product is free from defects in material and workmanship. This warranty does not apply to 
damage  caused by shipping or handling, or damage caused by accident, abuse, misuse, misapplication, ordinary wear, improper maintenance, failure to follow instructions or as a 
result of any unauthorized  modifications. If there is a defect in materials and workmanship under normal use within the warranty period Encore Controls   shall, at its option, repair or 
replace the defective equipment upon  return of the equipment to the original point of purchase. The foregoing warranty shall apply only to the original buyer, and is and shall be in 
lieu of any and all other warranties, whether expressed

 

or implied and of all other obligations or liabilities on the part of Encore Controls   neither assumes responsibility for, nor authorizes any other person purporting to act on its behalf to 
modify or to  change this warranty, nor to assume for it any other warranty or liability concerning this product. The maximum liability for Encore Controls   under all circumstances for 
any warranty issue shall be  limited to a replacement of the defective product. It is recommended that the customer check their equipment on a regular basis for proper operation.

 

 

THE LIABILITY OF ENCORE CONTROLS ,  OR ANY OF ITS PARENT OR SUBSIDIARY CORPORATIONS ARISING FROM THE SALE OF THIS SMOKE ALARM DETECTOR OR UNDER THE TERMS OF THIS 
LIMITED  WARRANTY SHALL NOT IN ANY CASE EXCEED THE COST OF REPLACEMENT OF A SMOKE ALARM DETECTOR AND, IN NO CASE, SHALL ENCORE CONTROLS ,  OR ANY OF ITS PARENT 
OR SUBSIDIARY  CORPORATIONS BE LIABLE FOR CONSEQUENTIAL LOSSES OR DAMAGES RESULTING FROM THE FAILURE OF THE SMOKE ALARM DETECTOR OR FOR BREACH OF THIS OR ANY 
OTHER WARRANTY, EXPRESS  OR IMPLIED, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE COMPANY’S NEGLIGENCE OR FAULT.

 

The Firefighter

 detector does not detect the presence of smoke, heat, or fire directly. It relies solely on the presence of an audio alarm signal generated by an existing smoke or fire detector in 

proximity to the Firefighter™ detector to make such a determination. The Firefighter™ detector must be used with smoke detectors certified according to UL Standards, and in strict accordance with 
the installation and operation instructions provided with such detectors. It is the owner’s responsibility to ensure that smoke or fire detectors used in conjunction with the Firefighter™ detector are 
maintained and tested on a regular basis in accordance with the manufacturer’s instructions. Encore Controls  expressly disclaims any responsibility for the failure of the Firefighter™ detector to detect 

Отзывы: