background image

EQUIPMENT:

   

FIRE

CLASS 

PRECEPT EN13

 

PUBLICATION:

  

FIRECLASS PREC EN13 INST

 

ISSUE No. & DATE:

 

2     22/07/2021

 

PAGE 15 of 32 

11.2  Commissioning Checklist 

1.  Before commissioning, the engineer should 

check the following: 
i)  All field wiring has been inspected and tested 

in accordance with Manufacturer’s  wiring 

recommendations, current issues of 

BS5839:1 and BS7671 IEE wiring 

regulations. 

ii)  All field cables are glanded into the control 

panel cabinet. 

iii) Detector bases are terminated but detector 

heads are not fitted. Any devices with 

electronic components are not fitted. 

Terminations to devices with electronic 

components should be linked through to 

maintain cable continuity. 

iv) Manual Call Points are not connected but 

cable is linked through to maintain continuity. 

v)  No end-of-line devices are fitted in the field. 

2.  The following information should be available to 

the commissioning team: 
i)  Detection layout drawings. 
ii)  Wiring schematic diagram. 
iii) Control Panel installation manuals. 
iv) Installation manuals for all equipment 

connected to the system. 

v)  Site specific configuration details. 
Experience has shown that tracing wiring faults 

on long circuits that are routed through risers 

etc. can be difficult without knowledge of the 

wiring route. 
It is recommended that the electrical installer be 

made available until basic wiring continuity is 

proven. A minimum of two persons (e.g. 

engineer and mate) is recommended for efficient 

commissioning. 

11.3  Commissioning Procedure Overview 

Commissioning is broken in to 3 sections: 
i)  Pre-commissioning wiring check. 
ii)  Powering the panel up with no field wiring 

connected, configuring the panel in accordance 

with the site-specific requirements and carrying 

out a functional check. 

iii)  Functional testing of all circuits and field devices 

to check each circuit and function in turn to 

ensure correct operation of the entire system. 

In this way any faults may be located quickly and 

accurately. The general procedures are as follows: 
1.  Alarm circuits should be checked first. The 

correct operation of each sounder should be 

checked for correct audibility as specified in 

BS5839:1, using the Evacuate function.  

2.  Detection zones should be commissioned next. 

The purpose is to establish the correct 

functioning of each device and checking for 

correct indication at the control panel. The panel 

responses as configured should be checked at 

this time. 

3.  All ancillary inputs and outputs should be 

commissioned and the functionality confirmed. 

4.  Fire protection signals should be tested. 
5.  Fire and fault routing signalling should be tested. 

WARNING: 

Before testing, the engineer must be 

aware both of the operation of all devices fitted to 

the auxiliary circuits and of the consequences of 

their operation. 

11.4  Pre-Commissioning Wiring Check 

NOTE: This pre-commissioning wiring check 

procedure should be followed to test all wiring 

prior to specific commissioning of any 

detection, alarm and auxiliary circuits. 
EN54-13 requires that the panel  is capable of 

detecting an increase in the cable resistance or 

a decrease in the resistance between cores (e.g. 

due to moisture ingress). It is therefore vital that 

the following cable checks are carried out 

carefully to ensure correct monitoring of the 

zone & alarm circuit cables. 

1.  Ensure that no devices are connected to the 

detection zones and alarm circuits, but that the 

cables are linked through at the device locations 

to achieve a continuous circuit. 

2.  Ensure that the resistance of all cables to earth 

and between cores is at least 2M

Check the following: 
i)  Positive to earth resistance is 2M

  or 

greater. 

ii)  Negative to earth resistance is 2M

  or 

greater. 

iii) Positive to negative resistance is 2M

  or 

greater. 

3.  Connect a wire link as the end-of-line device on 

each of the zones. At the panel end, measure 

the resistance across the positive & negative 

ends of the cables for each of the zone circuits, 

ensuring the value does not exceed 12

Remember to remove the wire links after the 

tests. 

4.  The alarm circuits should be wired in a loop with 

no EOL device. At the panel end, measure the 

resistance across the two  positive ends of the 

cable  and then the two negative ends of the 

cable for each of the circuits, ensuring the value 

does not exceed 6

Correct polarity throughout all circuits must be 

maintained. Rectify any faults. 

Содержание Precept EN13

Страница 1: ...UIPMENT FIRECLASS PRECEPT EN13 PUBLICATION FIRECLASS PREC EN13 INST ISSUE No DATE 2 22 07 2021 PAGE 1 of 32 Precept EN13 Fire Detection Alarm Panel Precept EN Repeater Installation Commissioning Manua...

Страница 2: ...RY DEFAULT CONFIGURATION FOR ZONES OUTPUTS 22 14 4 ENGINEER S ZONE OUTPUT CONFIGURATION TIME OUT WARNING 22 14 5 INVALID CONFIGURATION CONDITIONS 22 14 6 LIST OF CONFIGURATION DIL SWITCHES AND THEIR F...

Страница 3: ...this manual fully before commencing installation The following supporting documentation is also available FIRECLASS Precept EN13 Sales Literature FIRECLASS Precept EN13 Panel Application Guide FIRECLA...

Страница 4: ...3 2 1 ZONE CIRCUITS RST SIL EVAC CLASS CHANGE BUZ ACTIVE P A B REPEATER AUX D C 0V OUTPUTS INPUTS EVAC FAULT GND O ZONE OUTPUTS 4 3 2 1 24V 0V 2 1 3 01 05 12 ISSUE 0 CEL C1717 ALARM 4 3 2 1 CIRCUITS...

Страница 5: ...ACKBOX N L M a in s F u s e R ep la ce Sa m e Ty pe W ith RATING LABEL EARTH POST EARTH BAR MAINS TERMINAL ASSEMBLY RELAY BOARD Fu se In pu t Se ria l N o Pa rt N o Pr od uc t St an da rd s A pp ro va...

Страница 6: ...EQUIPMENT FIRECLASS PRECEPT EN13 PUBLICATION FIRECLASS PREC EN13 INST ISSUE No DATE 2 22 07 2021 PAGE 6 of 32 Figure 4 8 16 Zone Precept EN13 panel General Assembly with optional clock module...

Страница 7: ...iagram Connect to Aux DC 24V 24Vdc relay Typical zonal output wiring Field relay spec Coil resistance 2 6k to 4 5k Ohms Voltage 24Vdc Nom min 18V max 30V Fitted with suppression diode as shown Relay f...

Страница 8: ...les from Panel motherboard Each Alarm circuit from the panel motherboard is connected to the IN terminals on the Alarm Relay Board Each Alarm Circuit is wired out to the sounders from the OUT terminal...

Страница 9: ...le on selected panel Alarm Circuits 1 2 3 4 Aux DC 24V 0V SIL Inputs Outputs Repeater EVAC RST DIS EVAC A B GND Reset N C Inputs SIL Silence alarms EVAC Evacuate RST Reset Outputs DIS Disablement acti...

Страница 10: ...Terminals Power Supply LED indicators OUTPUT OK Battery Charger Fault Charger Fault Mains Fault J18 Earth Fault Monitoring Link Secondary AC from transformer C1631 Repeater Interface Alarm Circuits Ma...

Страница 11: ...tion resistance is greater than or equal to 1 the Batt Charge fault LED is illuminated and the Fault Output is operated The circuitry also protects against reversed connection of the batteries 9 2 Vis...

Страница 12: ...eat care when lifting and transporting batteries For weights above 24 kilos lifting aids should be used DANGER Do NOT attempt to remove the battery lid or tamper with the internal workings of the batt...

Страница 13: ...n an area that is clean dry and dust free where they will not be damaged You can place them inside the original packing box but you must ensure that sufficient soft packing is used to keep the door an...

Страница 14: ...y 26 Connect the blue battery lead between the positive red terminal of the left hand battery and the negative black terminal of the right hand battery Note that the batteries will not power the panel...

Страница 15: ...should be checked for correct audibility as specified in BS5839 1 using the Evacuate function 2 Detection zones should be commissioned next The purpose is to establish the correct functioning of each...

Страница 16: ...ise the mains and check the voltage and polarity are correct before replacing the panel fuse 4 The panel will power up and enter the power up cable check mode flashing System Fault LED After about 60...

Страница 17: ...nearest the panel operate each manual call point and detection device on the zone in turn o After operation of each device confirm The fire indication is provided on the panel on the correct zone The...

Страница 18: ...ed out at the appropriate time in conjunction with the engineer responsible for the fire protection system 11 7 6 Ancillary inputs Remote Silence Alarms Reset and Evacuate inputs should each be tested...

Страница 19: ...isabled Fault Routing Fault Disabled Yellow Flashes for a fault on the Fault Routing Output Steady when Fault Routing Output is disabled POWER SUPPLY ON FIRE FIRE ROUTING ACTIVE GENERAL FAULT POWER SU...

Страница 20: ...ked and if silence before reset is configured sounders are silenced Silence Buzzer 1 Press to stop the buzzer sounding in fire or fault conditions Always available 2 In 2 Stage Delay Mode with stage 1...

Страница 21: ...and the panel buzzer will silence A pulsing indication cursor will appear either on the Zone 1 Fault Disabled LED or the Sounder Fault Disabled LED Test depending upon which configuration DIL switch i...

Страница 22: ...e o The panel buzzer will sound o The Cursor indication will clear o Configuration will be inhibited To clear the invalid condition check the configuration switches SW1 4 to SW1 8 on the motherboard a...

Страница 23: ...1 minute within the range 0 9 minutes See Table 1 Motherboard Delay Switch Settings Table 1 Motherboard Delay Switch Settings Delay Duration SW2 2 SW2 3 SW2 4 SW2 5 NONE Off Off Off Off 1 minute On Of...

Страница 24: ...14 8 Configuring the Fire Routing Fire Protection and Fault routing O Ps To configure the Fire Routing Output to volt free relay contacts remove links J10 J11 and J12 These links are combined in a sin...

Страница 25: ...to 59 Press SELECT ON Time Set display HH MM SS ON Time SS flashing Press ENABLE or DISABLE to change SS to desired value 00 to 59 To set Day Night Mode Off Time Press SELECT to access day night OFF...

Страница 26: ...or EEPROM1 EEPROM 0 ERROR or EEPROM 1 ERROR Note Both EEPROMs can be erased by the following procedure 1 Power the panel down 2 Place the WP DIL switch in the ON position 3 Power the panel back up 4...

Страница 27: ...15 4 C1651 Clock Module PCB Features Figure 10 llustrates the PCB features referred to elsewhere in the documentation Figure 10 C1651 Clock Module PCB LK1 Select Operating Mode LK1 S1 WP ZERO 1 2 ON D...

Страница 28: ...Voltage 230Vac 10 15 Cable requirements Minimum of 1mm2 copper protected by a 5A fuse Power Supply Output Specification Panel Repeater AC powered 2 4 zone 8 zone 16 zone 2 4 8 16 zone Maximum Short T...

Страница 29: ...off PS12120 12V 12Ah 2 off PS12120 12V 12Ah 2 off PS12120 12V 12Ah 2 off PS1230 12V 3 4Ah Battery size mm L HT H W L 151 W 98 H 94 HT 100 L 151 W 98 H 94 HT 100 L 151 W 98 H 94 HT 100 L 133 W 67 H 60...

Страница 30: ...characteristics Performance under fire conditions Pass Response delay response time to fire Pass Operational reliability Pass Durability of operational reliability Temperature resistance Pass Durabil...

Страница 31: ...5 EN BSEN 54 4 Power supply equipment for fire detection and fire alarm systems for buildings List of essential characteristics Performance under fire conditions Pass Operational reliability Pass Dura...

Страница 32: ...2 07 2021 2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice Tyco Fire Security...

Отзывы: