Optical (sensitivity high, normal, or low) and
heat fixed temperature 60°C (A2S)
•
Heat only rate-of-rise (A1R) detector (no
sensitivity selection)
•
Heat fixed temperature 60°C (A2S) (no
sensitivity selection)
•
Heat rate-of-rise (A1R) detector and optical
smoke (sensitivity high, normal, or low)
•
HPO (Advanced) smoke detector (sensitivity
high, normal, or low)
•
HPO Enhanced with heat fixed temperature
60°C (A2S)
•
HPO Enhanced rate-of-rise (A1R).
FC460PC Addressable optical
smoke & heat detector & CO
The high performance FC460PC detector detects
smoke, temperature, and CO. It can accurately
determine the presence of all types of fires and has
an exceptional immunity to false alarms.
The functionalities of the FC460PC detector are:
Self-monitoring, self-testing, status indicator,
remote LED, and threshold compensation. FC460PC
is compatible with the existing bases.
FC410LI Line isolator module
The FC410LI line isolator module is designed to
be used on the FC addressable controller loop
circuits. It monitors the line condition and when
detecting a short circuit will isolate the affected
section while allowing the rest of the addressing
circuit to function normally.
The purpose of the FC410LI line isolator module is
to ensure that, on a looped addressable system,
no short circuit fault can disable more detection
devices then would be lost on a conventional non-
addressable fire circuit.
FC410MIM Mini input module
The FC410MIM mini input module is designed to
monitor fire contacts, such as extinguishing system
control, ventilation control, fire door control etc. The
module provides one identifiable detection spur
which is capable of monitoring multiple normally
open contacts or a single normally closed contact.
The FC410MIM may be mounted in any electrical
enclosure with sufficient depth to accommodate
FC410MIM and the contacts monitored by the IN+
and IN- terminals, i.e., no field wiring. The remote
LED (if required, not supplied) must be located
within the same electrical enclosure.
FC410MIO Small addressable
multi I/0 module
The FC410MIO multi I/O module has three class B
inputs and two outputs from latching relays. The
class B inputs can monitor fire contacts such as
extinguishing system control, ventilation control,
and fire door control. The two relays outputs are
dry form C that provide volt-free relay changeover
contacts. A maximum of two HVR800 high voltage
relay modules can be individually driven and
controlled by an FC410MIO if all HVR800s are
powered by 24VDC or 24VAC. In this application, the
HVR800s are controlled by the two latching relays
on the FC410MIO. A maximum of four HVR800 high
voltage relay modules can be individually driven
and controlled by an FC410MIO if all HVR800s are
powered by 120 VAC or 240 VAC. In this application,
the HVR800s are controlled by the four control
outputs (O1+/O1- to O4+/O4-) on the FC410MIO.
FC410SIO Single input and
output module
The FC410SIO single input and output module is
designed to provide a monitored open collector
input and a volt free relay changeover output.
FC410SIO can switch up to 2 A @ 24 VDC.
FC420CP Addressable break
glass callpoint (indoor)
The FC420CP addressable break glass callpoint is
designed to monitor and signal the condition of a
switch contact that is operated by activating the
break glass element. The type of alarm generated
by the callpoint is configured in the FireClass FC500
(FC501_FC503_FC506) Console. The FC420CP call
point meets the requirements of EN54 Pt.11. The
FC420CP is fitted to a standard surface mount
plastic back box, standard single gang metal plaster
box (35 mm for flush mounting) or standard single
gang metal plaster box (25 mm) with back box.
FC421CP Addressable break
glass callpoint (outdoor)
The FC421CP weatherproof addressable break
glass callpoint is designed to monitor and signal
the condition of a switch contact that is operated
by activating the break glass element. The type of
alarm generated by the callpoint is configured in
FC503 and FC506 Addressable Fire Control Panels