background image

4

Product application & Design information Doc. version 1.0 14 February 2012

FC400CH Addressable carbon mo heat detector

FireClass

4.5.1.2 EFFECT OF AIRFLOW ON SENSITIVITY

The signal status of the FC400CH detector has been specifically designed to be in-
sensitive to abnormal air velocities. The effect of normal air velocities upon sensi-
tivity is negligible.

4.5.1.3 EFFECT OF TEMPERATURE ON SENSITIVITY

The carbon monoxide detector incorporates temperature compensation and its
condition current will be substantially constant over its specified operating range.

4.5.1.4 EFFECT OF ATMOSPHERIC PRESSURE ON SENSITIVITY

The sensitivity of the detector is not effected by changes in atmospheric pressure
unless they happen very quickly ie explosions.

4.5.2 RESPONSE TO FIRE TESTS

The response of the FC400CH carbon monoxide detection element of the detector
to real or large-scale test fires will be dependent on the detection mode chosen
and the sensitivity set in the control unit.
Other factors however, such as the rate of development of the fire, and relative ox-
ygen supply are also important. The fire tests defined in prEN54 pt. 7 which are in-
tended for ionisation and optical detectors are less appropriate for carbon
monoxide fire detectors as their design means that they produce significant levels
of carbon monoxide only in their later stages.
However, the FC400CH using compensated carbon monoxide combined with
A1R heat (sensitivity High and Normal) mode, pass all tests laid down in prEN54 pt
7 including the fire tests.

4.5.3 HEAT DETECTOR

4.5.3.1 GENERAL

The performance of heat detectors is defined in European Standard prEN54-5.

5.

DETECTOR ADDRESS

The loop address of the detector is held in internal E

2

PROM which is pro-

grammed from the FC490ST Address Programmer.

+

Note: this device use one address only on the loop.

6.

ADDRESS FLAG

Refer to Fig.6. The address flag is used to identify the address and zone of the de-
tector.The address flags are supplied in one of two packs (address 1 - 127 or
128-255 , with a different colour for each loop) and are ordered separately from the
detector.The address flag is fitted to the bottom of the detector. When the detector
is fitted to the base and turned until fully located the address flag is then transferred
to the base. If the detector is removed from the base, the address flag remains with
the base.

7.

ORDERING INFORMATION

FC400CH Carbon Mo Heat detector.
Address Flag Labels - Loop A (White).
Address Flag Labels - Loop B (Yellow).

8.

RECYCLING INFORMATION

Customers are recommended to dispose of their used equipments (panels, detec-
tors, sirens, and other devices) in an environmentally sound manner. Potential
methods include reuse of parts or whole products and recycling of products, com-
ponents, and/or materials.

9.

WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT (WEEE)
DIRECTIVE

In the European Union, this label indicates that this product should
NOT be disposed of with household waste. It should be deposited at
an appropriate facility to enable recovery and recycling.

The manufacturer reserves the right to change the technical specifications of this
product without prior notice.

4.

TECHNICAL SPECIFICATION

4.1 MECHANICAL

Dimensions:

The overall dimensions are shown in
Fig.5 ( less base ).

Materials

Body,cover, and closure:

FR110 ‘BAYBLEND’ flame retardant.

Weight

Detector:

0.088kg

De Base:

0.152kg

4.2 ENVIRONMENTAL

Temperature

Operating:

-0

o

C to +55

o

C

Storage:

-20

o

C to +55

o

C

+

The detector may be operated for short periods between the limits of 0

o

C to

-20

o

C but with reduced performance.

+

The detector may be operated for short periods between the 55

o

C to

+70

o

C, prolonged use between these limits will degrade the performance and

shorten the life of the detector.

Relative Humidity:

95% ( non-condensing )

Shock:
Vibration:

prEN54 Pts. 5 and 7

Impact:
Corrosion:

prEN54 Pts.5 and 7

The detectors comply with Lloyd’s Register Test Specification Number 1 (1996).
Environmental Category ENV2 plus Salt Mist test.

4.3

ELECTROMAGNETIC COMPATIBILITY

The detector complies with the following:

Ø

product family standard EN50130-4 in respect of Conducted Disturbances, Radi-
ated Immunity, Electrostatic Discharge, Fast Transients and Slow High Energy;

Ø

EN50081-1 for Emissions.

4.4

ELECTRICAL CHARACTERISTICS

The following characteristics (Table 1) apply at 25

o

C and nominal supply voltage of

37.5V

unless otherwise specified.

Table 1: Electrical Characteristics

Characteristic

Min.

Typ.

Max.

Unit

Loop Voltage

20.0

-

40

V

Quiescent Current

-

275

305

µA

Alarm Current*

3

3.3

mA

* No remote indicator fitted

Addressable circuit voltage:
40V dc max. with addressable waveform (polarity conscious).

4.5

PERFORMANCE CHARACTERISTICS

4.5.1 CARBON MONOXIDE

The FC400CH carbon monoxide sensing element with base, forms an address-
able detector which transmits, to remote equipment, signals representing the state
of the sensing cell. The control equipment evaluates these signals against prede-
termined criteria and decides when an alarm condition should be signalled.The in-
formation given below therefore relates to the performance of the carbon
monoxide element of the detector simply as a transducer, since the system alarm
response is determined by the control unit.

4.5.1.1 RESPONSE TO CARBON MONOXIDE

The response to carbon monoxide will vary from detector to detector. For this rea-
son each detector is characterised on manufacture and calibration values are
stored in the internal detector memory. The controller will then normalise the out-
put signal from the detector such that the output is equivalent to 2.5 bits/ppm car-
bon monoxide above a threshold of 20 bits. Carbon monoxide may be present in
some environments under certain circumstances (high values of pollution or ex-
treme environmental conditions). However, the deviation is unlikely to be signifi-
cant compared with the alarm threshold level.

Содержание FC400CH

Страница 1: ...nse according to the type of detector configured in FireClass Console The mode of the detector may be Heat only detector A1R or A2S Carbon monoxide only detector sensitivity High Normal or Low Compensated carbon monoxide detector sensitivity High Normal or Low Compensated carbon monoxide sensitivity High or Normal combined with heat A1R Note Ø The heat detection grades are to EN54 5 Ø Normal and H...

Страница 2: ...WEEE DIRECTIVE In the European Union this label indicates that this product should NOT be disposed of with household waste It should be deposited at an appropriate facility to enable recovery and recycling The manufacturer reserves the right to change the technical specifications of this product without prior notice 4 TECHNICAL SPECIFICATION 4 1 MECHANICAL Dimensions The overall dimensions are sho...

Страница 3: ...SE SOCKEL CIRCUITO LED REMOTO REMOTE LED CIRCUIT TREIBER FÜR HINWEISLEUCHTE CIRCUITO D INTERFACCIA DELLA BASE FUNZIONALE FUNCTIONAL BASE INTERFACE CIRCUIT TREIBER FÜR FUNKTIONS SOCKEL ELEMENTO TERMOSENSIBILE HEAT ELEMENT TEMPERATUR ELEMENT ELEVATORE L BASE BASELINE LIFT VOR SPANNUNG SPECCHIO DI CORRENTE CURRENT MIRROR STROM SPIEGEL CONVERTITORE I V I TO V CONVERTER I U KONVERTER CELLA CELL MESSZEL...

Страница 4: ...serimento della linguetta indirizzo FIG 6 Fitting Address Label Carrier Dimensioni generali del rilevatore FC400CH Overall Dimensions of FC400CH detector FIG 5 Abmessungen des Melders FC400CH Sezione e vista superiore del rilevatore Sectioned and Top View of the detector FIG 4 Schnittdarstellung und Ansicht von oben FireClass Via Gabbiano 22 Z Ind S Scolastica 64013 Corropoli TE Italy Hillcrest Bu...

Отзывы: