5.4 Psuedo Points In FireClass

FireClass Fire detection system  FireClass Panels

28

Service and Maintenance Doc. 

version1

Field

Description

Address

Pseudo Point 43

Label

Walktest Sounders 

Use

Sounders are walktested 
using standard point 

 

commands as directed from 
the User Interface. 
This point is set and cleared 
surrounding that walktest to 
place a record into the panel 
log.

Table 23: Psuedo Point 43-Details

Field

Description

Address

Pseudo Point 44

Label

Inhibit Sound LED

Use

The system monitors the 

 

isolate status of sounder 
devices.
If all sounders are isolated this 
point is set, once one sounder 
is available the point is 
cleared.
The activation of this point 
inhibits the activation of the 
sounder LED. 
The goal is not to indicate on 
the front panel that sounders 
are active, when the system 
knows they are all isolated.

Table 24: Psuedo Point 44-Details

Field

Description

Address

Pseudo Point 45

Label

Commissioning

Use

The system monitors the 
commissioning states. If any 
are active this point is raised.

Table 25: Psuedo Point 45-Details

Field

Description

Address

Pseudo Point 46

Label

Download Required

Use

In network configurations all 
panels broadcast issue 
details relating to their core 
functionality. If this differs 
between panels then the 

 

network will not operate as 
intended and full upload may 
not be possible

Table 26: Psuedo Point 46-Details

Field

Description

Address

Pseudo Point 47

Label

Test Equipment

Use

This point is activated when 
FireClass Checker is 

 

connected to the panel.

Table 27: Psuedo Point 47-Details

Field

Description

Address

Pseudo Point 48

Label

Walktest Outputs

Use

This point is activated when 
an output test is started from 
the panel user interface.

Table 28: Psuedo Point 48-Details

Field

Description

Address

Pseudo Point 54

Label

Force Day Mode

Use

If the panel was in day mode 
and a panel restart is 

 

performed. This point is 

 

activated to return to panel to 
day mode.

Table 29: Psuedo Point 54-Details

Field

Description

Address

Pseudo Point 56

Label

Isolation For Test

Use

This point is activated if the 
menu option to isolate non-
LED outputs is selected.

Table 30: Psuedo Point 56-Details

Содержание FC-P-S

Страница 1: ...Service and Maintenance FC P S Doc version 1 22 March 2012 FireClass Addressable Fire Alarm Control Panels From Software version 21...

Страница 2: ...re reserved in particular but not limited to the rights of copying distribution and translation No portion of this documentation including the online help may be reproduced edited copied or distribute...

Страница 3: ...ments Non LED Outputs 13 3 5 Service Maintenance 13 3 5 1 Diagnostics 15 3 5 2 Calibrate DDM 16 3 5 3 Restart System 17 3 5 4 Switches 17 3 6 Configuration 18 3 6 1 Change Text 18 3 6 2 Insert Point 2...

Страница 4: ...Contents FireClass Fire detection system FireClass Panels 4 Service and Maintenance Doc version 1 5 5 General Fault Overview 30 5 5 1 Fault Conditions On Devices 30 5 6 System Fault 35...

Страница 5: ...and re configuration func tions of FireClass control panels as accessed from menu options Theinformationisapplicabletoanymemberofthe FireClass range of control panels The guide covers for example add...

Страница 6: ...logged on this user is automatically logged off 2 2 Access Levels After logging on you access the functions in the form of menu options displayed on the LCD The access level of your user ID will deter...

Страница 7: ...2 Engineer Service menu see User guide Supervisor Maintenance 13 Engineer Counters 13 Engineer Maintenance Request 14 Engineer Battery Test 14 Engineer S W Init Count 14 Engineer Project Numbers 14 En...

Страница 8: ...s not need changing For a 2 or 4 loop configured panel to change the loop highlight the loop setting and press key to increment it to the next loop or press key to move to the previous loop You press...

Страница 9: ...learing Panel Logs Clearing the control panel logs simultaneously effects the following Clearing the Event Log Resetting the Fire Cycle Count Resetting the Software Initialisation Count The Software I...

Страница 10: ...egisters 1 Open the front panel of the controller 2 On the CPU board fit a link to header H2 3 Press and hold the switch S1 until the WDOG LED flashes 4 Release S1 remove the link from H2 5 Press and...

Страница 11: ...int Counters Use this Loop Point Counters option to check that the panel configuration matches the physical state of the loop and to see the number of points on the loop This option appears abbreviate...

Страница 12: ...left side applies to points 2and 20 Only detected from right side applies to points 60 to 63 3 2 2 Loop Point Status Use this option to print the statuses of all the points of different loops that are...

Страница 13: ...which have been walk tested since panel installation When the count exceeds 64000 the count displays 64000 Site test counter counts the total number of devices which have been walk tested site wide a...

Страница 14: ...ted to S W Versions in the menu Use this option to see the version number of various items such as the firmware and bootrom A screen of the type shown in Fig 25 is displayed includes details on the ne...

Страница 15: ...a detector Choose the type of point and specify the address You then see the type of screen shown in Fig 28 Press the 1 key to force the point The control panel will now respond as if the device at t...

Страница 16: ...then back again before pressing the End key The polling continues until you press the End key You cannot select another device to poll until you have pressed the End key Change Address You mainly use...

Страница 17: ...dressable loop for example With the display showing Status Std Fault press the 1 key to switch to Status Fast Fault Press the 2 key to switch back In Fast Fault faults are reported immediately That is...

Страница 18: ...th the display showing Status As Config pressthe1 key to switch to Status Forced High Press the 2 key to switch back Note that for an RSM test to be valid these conditions must be met The sounder must...

Страница 19: ...the same type of text After making all your text changes select Back F1 to display the type of screen shown in Fig 35 The above procedure for making changes to the text is also applicable to the Zone...

Страница 20: ...Conflict and the insert operation is abandoned 3 6 3 Delete Point Use this Delete Point option to remove a point address First navigate to the address to be deleted and press Enter You now see a scree...

Страница 21: ...the loop choose Yes overwrite all and press Enter to accept the option The screen appears as shown in Fig 39 Fig 39 Autoconfigure OverwriteAll Click Abort to discard the process of overwriting the loo...

Страница 22: ...IP R10 BATTERY FAULT I P R11 MAINS SUPPLY I P R12 CHARGER FAULT I P R14 I O 2 R15 I O 1 R16 24V RESET Table 3 Local I O Real Points Point Detail P01 DATA PACKET ERROR P02 FIFO FULL P03 EA FIFO FULL P...

Страница 23: ...ED RBxxR16 BACKLIGHT INHIBIT Table 5 RBus Real Points Point Detail Table 4 Local I O Pseudo Points cont Point Detail RBxxR01 MPIM DISPLAY FAIL RBxxR02 MPIM ROM FAIL RBxxR03 MPIM RAM FAIL RBxxR06 BAD P...

Страница 24: ...system FireClass Panels 24 Service and Maintenance Doc version 1 4 4 Addressable Loop Point Detail P01 LOOP FAULT Table 8 Addressable Loop Pseudo Points Reference For Further information on Points ref...

Страница 25: ...into different faults depending on the device being monitored Examples include NO RESPONSE and RELAY STUCK The processing for these faults is fixed and not alterable by the user 5 4 Psuedo Points In F...

Страница 26: ...loop SPI channels This fault is also raised if the slave loop card is not fitted Table 12 Psuedo Point 8 15 Details Field Description Address Pseudo Point 25 Label FIM Bad Packet Use The main CPU comm...

Страница 27: ...etails Field Description Address Pseudo Point 32 Label RBus Circuit Fault Use The Remote Bus RBus connections on the FIM are split between RBus 0 and non zero nodes If faults are detected on all nodes...

Страница 28: ...es If any are active this point is raised Table 25 Psuedo Point 45 Details Field Description Address Pseudo Point 46 Label Download Required Use In network configurations all panels broadcast issue de...

Страница 29: ...address where the first point address is One instead here as the RBUS units can be addressed from 0 15 the first address is Zero Field Description Address Pseudo Point 0 15 Label RBUS Fault Use Used b...

Страница 30: ...ble below lists the fault states possible for standard points within FireClass These are noted in the description column The group assignments are those assigned in the FireClass Version 21 0 template...

Страница 31: ...Device Fault DEVICE FAULT The device is present and replying but the reply indicates a device error Thisisthecatchallwherea more meaningful fault can not be raised Table 36 Fault Conditions on Device...

Страница 32: ...Fault State and Logged Description Use within FireClass Version 21 Table 36 Fault Conditions on Devices Wiring Fault Short Circuit WIRING S C FAULT This fault applies to FC410CIM FC410DIM FC410BDM FC4...

Страница 33: ...ate which is required by the firmware No response from Alarm Control ALARM CTRL NO RESP FC410RIM and FC410SNM if configured as alarm control units Fault State and Logged Description Use within FireCla...

Страница 34: ...ode for alarm detection Fault State and Logged Description Use within FireClass Version 21 Table 36 Fault Conditions on Devices CO Element Fault CO ELEMENT FAULT Raised on FC460PC detectors when the C...

Страница 35: ...detects this and triggers System Fault The system is still function ing albeit with a corrupt or non existent display i e the pri mary fire display has been lost Safe State The following fault condit...

Страница 36: ...e memory a signature ndicating a System Fault has occurred Reset the system via watchdog timeout this will cause a System Fault indication Upon restart the Non Volatilememory is read the signa ture id...

Страница 37: ...FireClass Fire detection system FireClass Panels 5 6 System Fault Service and Maintenance Doc version 1 37...