6. INSTALLING THE DETECTOR HEAD

 

(1)  Align up the position of head to the base, see Figure 

4. 

(2)  Screw the detector head into the base in clockwise 

direction. 

 
 

 
 
 
 
 
 
 

 
7.LED STATUS INDICATION

 

There are 3 types of detector signaling: 
(1)  At the end of the start-up time (15 minutes), check 

that the GREEN LED flashes every 5 seconds. If 
the LED fails to flash, it indicates the detector is not 
operating. Check the wiring for the correct voltage. 
Replace the detector if necessary 

(2)  When the carbon monoxide is detected, the LED 

will change to a flashing RED, and will be 
accompanied by an alarm sound. 

(3)  When the internal fault is detected, a single short 

audible signal will be indicated every 30 seconds. 

 

8. ACTIONS TO TAKE WHEN THE ALARM 
SOUNDING

 

In case of harmful levels of CO gas being detected, 
your detector will go into a continuous full alarm. Try 
to take the following necessary actions immediately: 
(a)  If there is anyone experiencing the effects of 

carbon monoxide poisoning such as headache, 
dizziness, nausea or other flu-like symptoms, 
call the emergency services immediately. You 
should evacuate all the people in the premises 
immediately. Do a head count to check that 
everybody is accounted for. 

(b)  Do not re-enter the premises until the problem 

has been corrected and the CO gas has been 
dispersed out and a safe level is reached. 

(c)  If no symptoms exist, immediately ventilate the 

home by opening windows and doors. 
 

WARNING: Normally an activation of the detector 
indicates the presence of CO gas. 
 
CAUTION: This detector will only indicate the 
presence of CO gas at the sensor. However, you 
have to be aware that the CO gas may be present in 
other areas in the premises. 
 

9. ACTIONS TO TAKE AFTER THE PROBLEM 
BEING CORRECTED

 

When the amount of the CO gas presence in the 
premises has been corrected, the alarm from the 
detector should silence and the unit should reset 
automatically. 
 

10. MAINTENANCE AND TESTING OF CARBON 
MONOXIDE DETECTORS

 

A CO detector constantly monitors for any carbon 
monoxide under its normal operational conditions. 

The following maintenance procedures for gas 
detectors will assure its desired performance: 
(1)    Use a vacuum cleaner to clean the dust around 
the vent holes of gas detector cover. 
(2)    Carry out a regular or weekly test of gas 
detectors. This test should only be carried out if the 
LED flashes every 5 seconds. 
(a)    To test the detector, place a magnet as 
indicated in figure 5 on the front of the detector. The 
detector should sound and the LED will be a 
constant RED. 
(b)    Remove the magnet; the sounder should stop 
sounding and the LED will revert back to flashing 
GREEN every 5 seconds. 
 
 

 
 
 
 
 
 
 
 
 
11. SPECIFICATION: 
 

Gas Monitored 

CO 

Operating Voltage 

12-30Vdc 

Sensitivity 
(EN 50291) 

50ppm within 90 minutes 
100ppm within 40 minutes 
300ppm within 3 minutes 

Alarm Sounds 

85dB 

Operating Temp(

4.4

 

~

 40

 

Standby Current 

50 uA @24V 

Alarm Current 

30 mA @24V 

Output 

Relay Output 
(Dry connection output) 

 

12. WARNING AND LIMIATION

 

Note that CQR-983 series gas detector is not 
supposed to be used as smoke detector of fire alarm. 
In addition, a gas detector will operate normally 
under regular power supply; therefore, it will not 
detect when power is removed. The detector should 
be replaced every 5 years. 
 

WARRANTY INFORMATION

 

Under the normal operational conditions, the 
manufacturer provides a 2 year warranty for the 
sensor head of the gas detector and a one-year 
warranty for other parts for repairing without charge. 
Part and labour charge will be required after the 
warranty is expired. 
 
CQR Fire & Security 
125 Pasture Road, 
Moreton, 
Merseyside, 
CH46 4TH 
United Kingdom. 
Technical help:-+44 (0)151 606 6311,   
Sales:-+44 (0)151 606 1000 

www.cqr.co.uk

   

 

Figure 4. 

Detector head

Base

Short alignment mark

Long Alignment Mark

Figure 5. 

Place Test
Magnet Here

Sensor

LED

Отзывы: