5. TESTING
1.
All the alarm signal devices, releasing devices and
extinguisher systems should be disabled during the
test period and must be re-enabled immediately at the
conclusion of testing.
2.
After energising the detector head for approximately
one minute, check to see the indicator green LED
flashing once every 3~5 seconds (this may be difficult
in strong light as the flash is only dim). If green LED
fails to flash, it indicates the non-functioning of the
detector or faulty wiring. Re-check the wiring or replace
the detector if necessary.
SMOKE SENSOR TESTING
Allow smoke from a test smoke aerosol to enter the
detector-sensing chamber for at least 2-3 seconds.
When sufficient smoke has entered the chamber, the
detector will signal an alarm, this being visible by the
continuous illumination of the LED. Reset each detector
and/or control unit before attempting to test any
additional detectors on the same zone. If the alarm fails
in during this step, it indicates a defective unit, which
requires service/replacement.
HEAT SENSOR TESTING
The detector to be tested should be subject to a flow of
warm air at a temperature of between 65
°
C and 80
°
C or
by using a dedicated heat detector tester.
Proceed as follows:
a.
Switch on the warm airflow and check that
temperature is correct and stable.
b.
From a distance of several inches, direct the
airflow at the guard protecting the thermistor.
The detector should alarm within 30 seconds
c.
Upon alarm immediately remove the heat
source and check that the red LED of the
detector is illuminated. Reset the detector from
the control panel.
d.
If detector fails to go into alarm mode within 30
seconds it is too insensitive and needs to be
returned to the distributor for servicing.
3. If using a dedicated heat detector tester following the
manufacturer
’
s instructions.
4. After testing, check that the system is set for normal
operation and notify the appropriate authorities that the
testing operation is complete and the system is active
again.
NOT SUITABLE FOR INSTALLATION IN AREAS
WHERE AIR VELOCITIES EXCEED 300 ft/min
6. MAINTENANCE
The recommended minimum requirement for detector
maintenance consists of an annual cleaning of dust from
the detector head by using a vacuum cleaner.
CAUTION: DO NOT ATTEMPT TO DISASSEMBLE THE
FACTORY
SEALED
SMOKE
DETECTOR.
THIS
ASSEMBLY IS SEALED FOR YOUR PROTECTION AND
IS NOT INTENDED TO BE OPENED FOR SERVICING BY
USERS. OPENING THE DETECTOR CHAMBER WILL
VOID THE WARRANTY.
SPECIFICATION
Model
2/4
wire
Thermal
Voltage
DC
Standby
Current
(Max.)
Alarm
Current
(Max.)
Surge
Current
(Max.)
Star-Up
Time
(Max.)
Permissible
Current
(Max.)
LED Flash
Frequency
Remote Led
Option
Alarm
contact
Standard base
model number
Deep base
model number
CQR-338-2
2
28/12V
90
μ
A
70mA
120
μ
A
60
Seconds
80mA
3-5 Seconds
—
—
772912
882912
CQR-338-2L
2
28/12V
90
μ
A
70mA
120
μ
A
60
Seconds
80mA
3-5 Seconds
Yes
—
774912
882912
CQR-338-4-12
4
12V
320
μ
A
35mA
120
μ
A
60
Seconds
80mA
3-5 Seconds
—
Form A
774912
882912
CQR-338-4-24
4
24V
320
μ
A
35mA
120
μ
A
60
Seconds
80mA
3-5 Seconds
—
Form A
774912
882912
CQR-338-2H
2
57
°
C
28/12V
100
μ
A
70mA
130
μ
A
60
Seconds
80mA
3-5 Seconds
—
—
772912
882912
CQR-338-2HL
2
57
°
C
28/12V
100
μ
A
70mA
130
μ
A
60
Seconds
80mA
3-5 Seconds
Yes
—
774912
882912
CQR-338-4H-12
4
57
°
C
12V
320
μ
A
35mA
130
μ
A
60
Seconds
80mA
3-5 Seconds
—
Form A
774912
882912
CQR-338-4H-24
4
57
°
C
24V
320
μ
A
35mA
130
μ
A
60
Seconds
80mA
3-5 Seconds
—
Form A
774912
882912
Remarks:
H
=heat/
L
= Remote LED indicator output
LIMITED WARRANTY STATEMENT
ALL CQR PRODUCTS CARRY OUR STANDARD WARRANTY, PLEASE SEE CQR TERMS AND
CONDITION FOR FULL DETAILS.
CQR Security
125 Pasture Road, Moreton, Merseyside,
United Kingdom, CH46 4TH
Tel: - +44(0)151 606 1000 Fax: - +44(0)151 606 1122
e-mail:- [email protected] Web:- www.cqr.co.uk
Technical Support: - +44(0)151 606 6311
web:- www.cqr.co.uk Technical Support:- +44(0)1516066325
2531
web:- www.cqr.co.uk Technical Support:- +44(0)1516066325