Mounting
Indicator Preparation
17
Document 53244 Rev. A 03/14/08 P/N 53244:A
Section 3:
Mounting
3.1
Indicator Preparation
The LCD-80FC Indicator can be surface mounted in a three-gang elec-
trical box such as the P/N SBB-3 (2.75" depth) or semi-flush mounted in
a three-gang electrical box, P/N 10103 or equivalent, with a minimum
depth of 2 3/16". The LCD-80FC Indicator can also be mounted in three
gangable electrical switch boxes connected together. Select and remove
the appropriate knockout(s), pull the necessary wires through the knock-
outs and mount the box in or on the wall depending on the type of instal-
lation desired.
Be certain that power is not applied to the wiring during
the installation procedure.
Note: To ensure static protection, all enclosures, including the LCD-
80FC electrical box, must be connected to earth ground! Never use the
shield for grounding purposes.
To mount the LCD-80FC Indicator in an electrical box, the trim ring
must first be removed. The trim ring is held in place by two screws
inserted through the top and bottom edge as illustrated in Figure 3-1.
Removal of the trim ring will expose a metal flange with mounting
holes. Refer to “Hardware and Backboxes” on page 18.
Figure 3-1: Trim Ring Removal
Screw
Screw
LCD
-80
F
C
anada
.cd
r