FCPS-24FS Series Instruction Manual —
P/N 51883:H1 4/14/2011
35
Master FACP with Slave FCPS-24FS Power Supply
Applications
5.5 Master FACP with Slave FCPS-24FS Power Supply
In this application, an FCPS-24FS power supply, configured as a Slave unit, is connected to a mas-
ter FACP programmed for synchronized output. The power supply should be set for synchroniza-
tion which matches the FACP programming.
The following notes apply to both illustrations in Figure 5.5 on page 35
1. Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2. Use only devices from the same manufacturer in each system.
3. If the FACP has a dedicated sync output connector, wire the remote sync output connector to
the FCPS Sync In terminals TB4 terminals 1 & 2. Refer to the Supervised Master/Slave
Connections (Remote Sync Source) in Figure 5.5b.
-
+
TB
4
JP
3
J3
TB
5
TB
2
JP
1
JP
2
OU
T4
-N
A
C
4+
OU
T3
-N
A
C
3
+
OU
T2
-N
AC2
+
OU
T1
-N
A
C
1+
AU
X
-
IN
2-
IN
2+
OU
T1
-
OUT1+
IN
1-
IN
1+
S
Y
NC I
N
-
SY
N
C
IN
+
AUX
+
NO
N
C
AU
X
T
B
L
CO
M
1 2 3 4 5 6 7 8 9 10
8
7
6
5
4
3
2
1
3
2
1
ELR
-
+
TB
4
JP
3
J3
TB
5
TB2
JP
1
JP
2
OU
T
4
-NAC
4+
OU
T
3
-N
A
C
3
+
OU
T2
-NAC2
+
OU
T1
-NAC1+
AU
X
-
IN
2
-
IN
2
+
OU
T1-
OU
T
1
+
IN
1-
IN
1
+
SYN
C I
N
-
SYNC
IN
+
AUX
+
NO
N
C
AU
X
TB
L
CO
M
1 2 3 4 5 6 7 8 9 10
8
7
6
5
4
3
2
1
3
2
1
ELR
Standby Polarity Shown
FCPS-24FS
SW1 Switch Settings
1 & 2 = sync (any setting
but OFF/OFF)
3 = ON (slave)
4 = OFF (no AC Fail
reporting delay)
5 = OFF
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
Figure 5.5 Supervised Master/Slave Connections
general alarm
24
fs
ap
p1
c.
wmf
See Note 3
24
fsa
pp1
b.w
m
f
SW1 Switch Settings
1 & 2 = sync (any setting
but OFF/OFF)
3 = ON (slave)
4 = OFF (no AC Fail
reporting delay)
5 = OFF
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
Figure 5.5a: Supervised Master/Slave Connections (Filtered, Synchronized NAC Source)
Figure 5.5b: Supervised Master/Slave Connections (Remote Sync Source)
Standby Polarity Shown
FACP
NAC1
(programmed
for sync)
Internal Trouble
Contact
FACP
Remote Sync
Output
Internal Trouble
Contact