Emergency Command Center Manual —
P/N LS10001-000FL-E:D 9/3/2014
99
Appendix C: Canadian Applications
When using the ECC in Canadian Applications, note the following:
•
The ECC-50/100 is for fire evacuation use only.
•
The ECC-50DA, ECC-125DA, and ECC-50BDA amplifiers are not permitted for use in
Canada.
•
The ECC-RPU and ECC-RM are not permitted for use in Canada.
•
The ECC-50/100 must be mounted next to the FACP.
C.1 Audio Room Isolator Modules
C.1.1 Description
The audio isolator modules described below may be used to isolate short circuits during alarm sig-
naling.
AIM-1A
This module provides isolation to a separate circuit on an audio riser. A short circuit on
an AIM-1A speaker circuit will not disable other speaker circuits on the riser.
RSM-1A
This module works the same as the AIM-1A, with the exception that there is a silence
button for in-suite operation. The silence button will silence the audible signal to the module’s cir-
cuit for ten minutes during alarm. Resounding will occur automatically after ten minutes or upon
activation of a new audio alert.
C.1.2 Panel Programming
“Canadian Configuration” and “Canadian Isolator Modules” must be enabled in ECCNFC pro-
gramming. Refer to “General/NAC Options” on page 61. In addition, “NAC Type” must be set for
steady operation. See “NAC Options” on page 62.
Содержание ECC-100
Страница 102: ...102 Emergency Command Center Manual P N LS10001 000FL E D 9 3 2014 Slide in Labels...
Страница 104: ...104 Emergency Command Center Manual P N LS10001 000FL E D 9 3 2014 Slide in Labels...
Страница 110: ...Cut along dotted line...
Страница 112: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com...