Emergency Command Center Manual —
P/N LS10001-000FL-E:D 9/3/2014
61
Main Menu - User Programming
Programming
Log Out
When all programming has been successfully completed, the user must log out to allow
the system to reboot and apply the programming changes.
3.1.2 General/NAC Options
General Options
Unit Operation
Select whether the ECC will function for
Fire Evacuation
,
Mass Notification
, or
a
Combination
of both.
Event Priority
When
Combo
or
Mass Notification
is selected for Unit Operation, select whether
Mass Notification
events or
Fire Evacuation
events will take priority in the system. If
Mass Notifi-
cation
is selected as the Unit Operation with the Event Priority set to
Fire Evacuation
, the ECC will
be a mass notification only system but will allow the FACP to override it if a fire alarm sounds. If
Mass Notification
is selected as the Unit Operation with the Event Priority also set to
Mass Notifi-
cation
, the ECC will not have any fire evacuation capabilities and will report mass notification
events to the FACP. In this configuration, FACP outputs can be turned off for mass notification
events if desired.
FACP Data Bus Control
If an FACP will directly communicate with the ECC, select which
communication protocol will be used,
ACS-Bus
or
ANN-Bus
.
FACP Data Bus Address
This field has no effect on programming and is used for informa-
tional purposes only.
When using the FACP ACS-bus protocol, address
01
must be enabled in the
FACP programming. When using the ANN-Bus protocol, the FACP will automatically detect the
audio system connection during annunciator auto-configuration. No ANN-Bus address selection is
necessary at the FACP. Enter the ECC’s address (1-8) here. If FACP control of the ECC is not
selected, enter
0
.
24 Hour Resound
As
enabled
(default), the 24 Hour Resound feature causes the piezo on the
ECC to sound a reminder ‘beep’ for alarms and troubles after the panel has been silenced.
Canadian Configuration
Selecting
enable
will configure the panel to comply with Canadian
requirements. See Appendix C for more information.
Class A / Style Z
Select
enable
if all circuits on the ECC will operate in Class A (Style Z) or
dis-
abled
if all circuits will operate in Class B (Style Y).
Canadian Isolator Modules
If audio isolator modules are required in the system, select
enabled
. Refer to “Audio Room Isolator Modules” on page 99 for more information.
Figure 3.3 General Options
ge
ne
ra
lo
p2
.jp
g
Содержание ECC-100
Страница 102: ...102 Emergency Command Center Manual P N LS10001 000FL E D 9 3 2014 Slide in Labels...
Страница 104: ...104 Emergency Command Center Manual P N LS10001 000FL E D 9 3 2014 Slide in Labels...
Страница 110: ...Cut along dotted line...
Страница 112: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com...