Audio Command Center Series Manual —
P/N 51889:E1 6/8/2010
87
ACC-25/50ZS & ACC-25/50ZST Zone Splitting Applications
Application Examples
5.5 ACC-25/50ZS & ACC-25/50ZST Zone Splitting
Applications
5.5.1 25 Watt Zone Splitting - Eight Speaker Circuits, Style Y
(Class B)
25 watts total power with automatic control via ACS link from FACP (see Table 2.7 on page 37,
Table 2.8 on page 40 and “ACC-ZSM Zone Splitter Module (ACC-25/50ZS & ACC-25/50ZST)”
on page 41 for settings).
This application of the ACC-25/50ZS & ACC-25/50ZST configures the Zone Splitter Module
(ACC-ZSM) to divide 25 watts of audio from one Audio Amplifier (ACC-AAM25) into eight
speaker circuits. The FACP uses the ACS link connected to the Zone Page Module (ACC-ZPMK)
for automatic activation of the speaker zones and for alarm activation.
Configuration switches are set as follows:
•
ACC-ZSM SW1 set to
AAM1
and SW2 to
Class B
to split one ACC-AAM25 into 8 Style Y
(Class B) zones
•
ACC-ZPMK DIP switch S1 set for communication with:
MS-9200UDLS or MS-9200UD with software version 2.x (1=ON, 2=OFF, 3=ON)
MS-9600 with software version 2.x or higher (1=ON, 2=OFF, 3=OFF)
•
ACC-25/50ZS main circuit board DIP switch S3 set for single zone mode, All-Call and two
messages (1=ON, 2=OFF, 3=OFF)
The MS-9600, MS-9200UDLS, or MS-9200UD FACP can
automatically activate
the Fire Evacua-
tion or All Clear Message and any combination of the 8 speaker zones.
Manually deactivating
a
speaker circuit is accomplished by pressing the activated zone push-button on the ACC-ZPMK
keypad.
Manual activation
can be performed by pressing either of the Message push-button(s) and
then selecting the zone push-button on the ACC-ZPMK keypad.
All-Call Paging
is possible by
first pressing the All-Call push-button on the main panel keypad and then keying the microphone to
make an announcement.
Содержание ACC-25
Страница 62: ...62 Audio Command Center Series Manual P N 51889 E1 6 8 2010 Notes ...
Страница 101: ...Audio Command Center Series Manual P N 51889 E1 6 8 2010 101 Notes ...
Страница 137: ...Audio Command Center Series Manual P N 51889 E1 6 8 2010 137 Notes ...
Страница 144: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...