Installation
Output Circuits
In Example 1 illustrated below, the ACC-25/50 Series panel will trigger the ACC-25/50DA(s)
when All-Call is activated for emergency or general paging.
The maximum line resistance from the main ACC-25/50 Series to the last ACC-25/50DA is 200
ohms (100 ohms per conductor).
The MR-101C (one Form-C relay) and MR-201C (two Form-C relays), which are manufactured by
Air Products and Controls, include an enclosure.
Figure 3.8 Example 1 - Activating Multiple ACC-25/50DAs with Master CMD Output Bus
4.7K
P/N: 27072
(Alarm polarities shown)
Activated when the All-
Call button, remote
microphone key or
External Page Module
is pressed (single zone
configuration only)
ACC-25/50DA
ACC-25/50 Series
ac
25o
ut.wmf
Master CMD
Output Bus
ACC-25/50DA
Master CMD
Bus In/Out
Master CMD
Bus In/Out
Style Z (Class A)
Figure 3.9 Example 2 - Activating MR-101C (or MR-201C) with Master CMD Output Bus
Relays may be used to activate an FACP initiating circuit.
CAUTION!
All wiring to relay must be in same room within
20 feet of FACP and in conduit.
Relay Energized LED
SPDT Contacts
10 amps @ 115 VAC
a
c2
5
m
r1
0
.w
m
f
Master ACC-25/50 Series
Activated when the All-Call button,
remote microphone key or External
Page Module is pressed (single
zone configuration only)
Содержание ACC-25
Страница 62: ...62 Audio Command Center Series Manual P N 51889 E1 6 8 2010 Notes ...
Страница 101: ...Audio Command Center Series Manual P N 51889 E1 6 8 2010 101 Notes ...
Страница 137: ...Audio Command Center Series Manual P N 51889 E1 6 8 2010 137 Notes ...
Страница 144: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...