Fire-Lite Alarms SD355CO Скачать руководство пользователя страница 2

B.  Smoke Entry:

 

 For SD355CO, smoke entry testing should be performed immediately fol-
lowing the magnet test. Magnet test initiates an approximately 10 minute 
period when the detector’s signal processing software routines are not 
active. Failure to first perform the magnet test will introduce a time delay 
before the detector alarms.

  

Aerosol Generator (Gemini 501)

 The GEMINI model 501 aerosol genera-

tor can be used for smoke entry testing. Set the generator to represent 
4%/ft to 5%/ft obscuration as described in the GEMINI 501 manual. Us-
ing the bowl shaped applicator, apply aerosol until the panel alarms.

 

 Canned Aerosol Simulated Smoke.

 Additionally, canned aerosol simu-

lated smoke (canned smoke agent) may be used for smoke entry testing 
of the smoke detector. Tested and approved aerosol smoke products are: 

 

 When used properly, the canned smoke agent will cause the smoke de-
tector to go into alarm. Refer to the manufacturer’s published instruc-
tions for proper use of the canned smoke agent.

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary by 
manufacturer. Misuse or overuse of these products may have long term adverse 
effects on the smoke detector. Consult the canned smoke agent manufacturer’s 
published instructions for any further warnings or caution statements.

C.  Direct Heat Method (Hair Dryer of 1000-1500 watts)

 

 A hair dryer of 1000-1500 watts should be used to test the thermistors. Di-
rect the heat toward either of the two thermistors, holding the heat source 
approximately 12 inches from the detector in order to avoid damaging 
the plastic housing. The detector will reset only after it has had sufficient 
time to cool. Make sure both thermistors are tested individually.

D.  Multi-Criteria Testing

 

 Testifire® by SDi provides testing of the smoke, heat and CO sensors.  Consult 
the manufacturer’s published instructions for complete usage instructions.

A sensor that fails any of these tests should be cleaned as described under 
CLEANING, and retested. If the sensor fails after cleaning, it must be replaced.
When testing is complete, restore the system to normal operation and notify 
the proper authorities that the system is back in operation.

FUNCTIONAL GAS TEST

NOTE: Check with local codes and the AHJ to determine whether or not a 
functional gas test is desired for an installation.
A canned CO testing agent may be used to verify the detector’s ability to 
sense CO. Tested and approved canned CO testing agent is solo detector tes-
ters model C6 CO Detector Tester available from SDi. Initiate the CO testing 
feature of the detector as follows:

1.   Put the device into test mode by holding a test magnet in the magnet test 

area as shown in Figure 3 for 6-12 seconds.

NOTE: If the magnet is held in place for too long the fire alarm test function 
will be triggered.  Reset the panel and proceed with testing the CO portion of 
the device. It may be preferred to put the device into fire alarm first via the 
magnet test to ensure the device has successfully entered test mode.

2.   Spray a UL approved CO agent into the top ring of the detector’s gas en-

try ports within 1/4” of the detector for at least 1 second (see Figure 4). It 
is recommended to use the applicator straw included with the CO agent 
to more efficiently direct the CO into the detection cell during testing. 

3.   The detector will go into alarm if gas entry is successful. It may take up 

to 1 minute for the device to alarm. Once the detector is in alarm allow 5 
minutes for the CO to clear and exit the detector.

The dector will automatically enable the signal processing after 10 minutes.

Testing the detector will activate the alarm relay and send a signal to the panel.

CAUTION: This carbon monoxide detector is designed for indoor use only. 
Do not expose to rain or moisture. Do not knock or drop the detector. The 
detector will not protect against the risk of carbon monoxide poisoning if not 
properly wired. The detector will only indicate the presence of carbon mon-
oxide gas at the sensor. Carbon monoxide gas may be present in other areas.

This carbon monoxide detector is NOT:

•  Designed to detect any gas other than carbon monoxide

•  To be seen as a substitute for the proper servicing of fuel-burning appli-

ances or the sweeping of chimneys.

•  To be used on an intermittent basis, or as a portable alarm for the spill-

age of combustion products from fuel-burning appliances or chimneys.

Carbon monoxide gas is a highly poisonous gas which is released when fuels 
are burnt. It is invisible, has no smell and is therefore impossible to detect with 
the human senses. Under normal conditions in a room where fuel burning 
appliances are well maintained and correctly ventilated, the amount of carbon 
monoxide released into the room by appliances should not be dangerous.

Symptoms of carbon monoxide poisoning:

 Carbon monoxide bonds to the 

hemoglobin in the blood and reduces the amount of oxygen being circulated 
in the body. The following symptoms are examples taken from NFPA 720. 
They represent approximate values for healthy adults: 

Concentration (ppm CO)

Symptoms

200

Mild headache after 2-3 hours  

of exposure

400

Headache and nausea after  

1-2 hours of exposure

800

headache, nausea, and dizziness 

after 45 minutes of exposure;  

collapse and unconsciousness after 

2 hours of exposure

SENSOR COVER

SPRAY AEROSOL 

CO HERE INTO 

TOP RING

COVER 

REMOVAL 

TABS

FIGURE 4. CO TESTING:

C0952-01

FL-400-006  2 I56-4129-000

MANUFACTURER

MODEL

Home Safeguard Industries

25S

SDi

CHEK02 and CHEK06

SDi

SOLOA4

SDi

SMOKESABRE-01

TEST 

MAGNET

FIGURE 3. TEST MAGNET POSITION:

C0951-00

Содержание SD355CO

Страница 1: ...move power from the communication line before installing sensors 1 Wire the sensor base supplied separately per the wiring diagram see Figure 1 2 Set the desired address on the sensor address switches see Figure 2 3 Install the sensor into the sensor base Push the sensor into the base while turning it clockwise to secure it in place SPECIFICATIONS Operating Voltage Range 15 to 32 VDC Standby Curre...

Страница 2: ... in Figure 3 for 6 12 seconds NOTE If the magnet is held in place for too long the fire alarm test function will be triggered Reset the panel and proceed with testing the CO portion of the device It may be preferred to put the device into fire alarm first via the magnet test to ensure the device has successfully entered test mode 2 Spray a UL approved CO agent into the top ring of the detector s g...

Страница 3: ...essed air to remove dust and debris from the sensing chamber and sensing chamber cover 6 Re install the sensing chamber cover assembly by sliding the cover over the chamber gently pressing it home until it snaps into place 7 Re install the sensor cover Use the cover removal tabs LEDs and therm istors to align the cover with the sensor Snap the cover into place 8 When all sensors have been cleaned ...

Страница 4: ...iate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installa tion If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is enc...

Отзывы: