Fire-Lite Alarms SD355CO Скачать руководство пользователя страница 1

FL-400-006  1 I56-4129-000

SD355CO Multi-Criteria CO and Smoke Sensor

INSTALLATION AND MAINTENANCE INSTRUCTIONS

BEFORE INSTALLING

This sensor must be installed in compliance with the control panel system 
installation manual. For local audible indication of a fire and/or carbon 
monoxide alarm, it is recommended to install the SD355CO detector into a 
B200S series sounder base. If a local audible device is not used, care should 
be taken to develop a proper response plan. The installation must meet 
the requirements of the Authority Having Jurisdiction (AHJ). Sensors offer 
maximum performance when installed in compliance with the National Fire 
Protection Association (NFPA); see NFPA 72 and NFPA 720. For a complete 
list of compatible bases, refer to the Base/Sensor Cross Reference Chart at  
systemsensor.com.

GENERAL DESCRIPTION

Model SD355CO is a plug-in type smoke sensor that is a photoelectronic sens-
ing chamber combined with carbon monoxide (CO), thermal and infra-red (IR) 
sensors as well as a carbon monoxide detector both with addressable-analog 
communications. The sensors transmit an analog representation of smoke 
and/or carbon monoxide density over a communication line to a control panel. 
Rotary-decade switches are provided for setting the sensor’s address.

Two LEDs on the sensor are controlled by the panel to indicate sensor status. 
An output is provided for connection to an optional remote LED annunciator 
(P/N RA400Z /RA100Z).

The SD355CO requires compatible addressable communications to function 
properly. Connect these sensors to listed-compatible control panels only.

SPACING

Fire-Lite recommends spacing sensors in compliance with NFPA 72. In low 
air flow applications with smooth ceilings, space sensors 30 feet apart. For 
specific information regarding sensor spacing, placement, and special appli-
cations, refer to NFPA 72 or the 

System Smoke Detector Application Guide

,

 

available from Fire-Lite.

TAMPER-RESISTANCE

Models SD355CO includes a tamper-resistant capability that prevents removal 
from the bracket without the use of a tool. Refer to the base manual for details 
on making use of this capability.

WIRING GUIDE

All wiring must be installed in compliance with the National Electrical Code, 
applicable local codes, and any special requirements of the Authority Having 
Jurisdiction. Proper wire gauges should be used. The installation wires should 
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the 
event of a fire.

Remove power from the communication line before installing sensors.

1.   Wire the sensor base (supplied separately) per the wiring diagram, see 

Figure 1.

2.   Set the desired address on the sensor address switches, see Figure 2.
3.   Install the sensor into the sensor base. Push the sensor into the base 

while turning it clockwise to secure it in place.

SPECIFICATIONS 

Operating Voltage Range: 

15 to 32 VDC

Standby Current: 

300µA @ 24 VDC (one communication every 5 sec. with LED blink enabled)

Max. Alarm Current (LED on:) 

7 mA @ 24 VDC

Operating Humidity Range:  

15% to 90% Relative Humidity, Non-condensing

Operating Temperature Range: 

0°C to 38°C (32°F to 100°F)

Height:  

2.7˝ (69 mm) installed in B200S Base*

Diameter: 

6.875˝ (175 mm) installed in B200S Base*

Weight:   

4.6 oz. (130 g)

SMOKE SENSOR TESTING

Before testing, notify the proper authorities that the system is undergoing 
maintenance, and will temporarily be out of service. Disable the system to 
prevent unwanted alarms.

All sensors must be tested after installation and periodically thereafter. Testing 
methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors offer max-
imum performance when tested and maintained in compliance with NFPA 72. 

The sensor can be tested in the following ways:

A.  Functional: Magnet Test (P/N M02-04-01 or M02-09-00)

 

 This sensor can be functionally tested with a test magnet. The test mag-
net electronically simulates smoke in the sensing chamber, testing the 
sensor electronics and connections to the control panel.

 

1.   Hold the test magnet in the magnet test area as shown in Figure 3.

 

2.  The sensor should alarm the panel.

 

 Two LEDs on the sensor are controlled by the panel to indicate sensor 
status. Coded signals, transmitted from the panel, can cause the LEDs 
to blink, latch on, or latch off. Refer to the control panel technical docu-
mentation for sensor LED status operation and expected delay to alarm.

I56-4

129-000

(+) COMM.

(–) COMM.

(–) POWER

(+) POWER

U.L. LISTED COM

PA

TIBLE

CONTROL

 P

ANEL

EXTERNAL 24V SUPPL

Y

OPTIONAL REMOTE ANNUNCIATOR

1

2

3

4

5

6

1

2

3

4

5

6

1

2

3

4

5

6

FIGURE 1. WIRING DIAGRAM:

C0474-02

FIGURE 2. ROTARY DECADE ADDRESS SWITCHES:

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

C0162-00

CAUTION

Dust covers provide limited protection against airborne dust particles during 
shipping. Dust covers must be removed before the sensors can sense smoke or 
carbon monoxide. Remove sensors prior to heavy remodeling or construction.

*For additional compatible bases, refer to the Base/Sensor Cross Reference 
Chart at systemsensor.com.

4.   After all sensors have been installed, apply power to the control unit and 

activate the communication line.

5.   Test the sensor(s) as described in the TESTING section of this manual.

One FireLite Place

Northford, CT 06472

Phone: 203.484.7161 

Содержание SD355CO

Страница 1: ...move power from the communication line before installing sensors 1 Wire the sensor base supplied separately per the wiring diagram see Figure 1 2 Set the desired address on the sensor address switches see Figure 2 3 Install the sensor into the sensor base Push the sensor into the base while turning it clockwise to secure it in place SPECIFICATIONS Operating Voltage Range 15 to 32 VDC Standby Curre...

Страница 2: ... in Figure 3 for 6 12 seconds NOTE If the magnet is held in place for too long the fire alarm test function will be triggered Reset the panel and proceed with testing the CO portion of the device It may be preferred to put the device into fire alarm first via the magnet test to ensure the device has successfully entered test mode 2 Spray a UL approved CO agent into the top ring of the detector s g...

Страница 3: ...essed air to remove dust and debris from the sensing chamber and sensing chamber cover 6 Re install the sensing chamber cover assembly by sliding the cover over the chamber gently pressing it home until it snaps into place 7 Re install the sensor cover Use the cover removal tabs LEDs and therm istors to align the cover with the sensor Snap the cover into place 8 When all sensors have been cleaned ...

Страница 4: ...iate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installa tion If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is enc...

Отзывы: