OSI-RI by Fire-Lite Alarms
OSI-RI-FL Installation Guide
E56-6584-001 | October 2018
35
14 Operation After A Power Failure
The detector has the reflector location/position, set sensitivity and other commissioning parameters
permanently memorised after the initialisation process.
After a power failure of any duration, when the supply is restored the detector will check the possible new
situation versus it memorised data.
If the reflector is found in the same position and all parameters are within acceptable limits, the detector will
resume its operation and go out of fault condition.
If any significant parameters have changed, it will remain in a fault condition and a re-initialisation will be
required.