Correlations
NFPA Standard-Specific Requirements
MS-9200UD PN 51906:A 12/10/02
177
NFPA 72 Remote Station Protective Signaling System
Notes:
1. Cut Jumper JP3 on the MS-9200UD main circuit board to supervise placement of
the 4XTMF module.
2. Refer to "4XTMF Transmitter Module Installation" on page 38 for detailed
information.
Fire•Lite RS82 Remote Station Receiver UL listed.
Refer to Fire•Lite Instruction Manual for Remote Station
Receiver Model RS82.
+ -
Polarity Shown is
Normal Standby
4XTMF Transmitter Module
Cutting TBL Jumper allows the
reverse polarity circuit to open
with a system trouble condition
if no alarm condition exists.
Power-limited
Figure C.2 Remote Station Connection Using 4XTMF Module
+
-
(Dummy load with a 4.7K
Ω
, ¼ watt
resistor when no connection is made
)