This  sensor  must  be  installed  in  compliance  with  the  control  panel  system 
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when 
installed in compliance with the National Fire Protection Association (NFPA); 
see NFPA 72.

Before installing sensors, please read the system wiring and installation man-
ual  thoroughly.  This  manual  provides  detailed  information  on  sensor  spac-
ing, placement, zoning, and special applications. Copies of these manuals are 
available from Fire-Lite.

GENERAL DESCRIPTION

Models H355, H355R, and H355HT are intelligent sensors that utilize a state-
of-the-art thermistor sensing circuit for fast response. These sensors are de-
signed  to  provide  open  area  protection  with  50  foot  spacing  capability.  For 
installations which must comply with FM3210, see note below. Model H355 is 
a fixed temperature sensor with 135° F fixed temperature alarm. Model H355R 
is  a  rate-of-rise  temperature  sensor  with  135°  F  fixed  temperature  alarm. 
Model H355HT is a high temperature sensor with 190° F fixed temperature 
alarm.

Two LEDs on each sensor light to provide a local, visible sensor indication. 
Remote LED annunciator capability is available as an optional accessory (Part 
No. RA400Z).

Models H355, H355R, and H355HT require compatible addressable com-
munications to function properly. Connect these sensors to listed-compat-
ible control panels only.
NOTE:  Per FM3210

The H355 and H355HT are classified as fixed temperature thermal detectors: 

A thermal detector that responds when the operating element of the detector 
reaches a specified temperature.  The actual temperature surrounding the sens-
ing element is often much greater than the rated temperature due to the ther-
mal lag.

The  H355R  is  classified  as  a  rate-compensated  thermal  detector: 

A  thermal 

detector that responds to a specified fixed temperature, regardless of the rate of 
temperature rise.

WIRING GUIDE

All wiring must be installed in compliance with the National Electrical Code, 
applicable  local  codes  and  the  Authority  Having  Jurisdiction.  Proper  wire 
gauges should be used. The installation wires should be color coded to limit 
wiring mistakes and ease system troubleshooting. Improper connections will 
prevent a system from responding properly in the event of a fire.

Remove power from the communication line before installing sensors. 

1.   Wire  the  sensor  base  (supplied  separately)  per  the  wiring  diagram, 

see Figure 1.

2.  Set the desired address on the sensor address switches, see Figure 2.
3.   Install  the  sensor  into  the  sensor  base.  Push  the  sensor  into  the  base 

while turning it clockwise to secure it in place. 

4.   After all sensors have been installed, apply power to the control unit and 

FL-400-001 

I56-3657-002R

I56-3657-00

2R

H355, H355R, and H355HT 
Intelligent Plug-In Temperature Sensors

SPECIFICATIONS

Diameter: 

6.1˝ (155 mm) installed in B350LP

Height: 

2.0˝ (51 mm)

Weight: 

4.8 ounces (137 gm)

Installation Temperature: 

–4°F to 100°F (–20°C to 38°C), H355 and H355R; –4°F to 150°F (–20°C to 66°C), H355HT

Operating Humidity Range: 

10% to 93% Relative Humidity, Non-condensing

Mounting: 

B350LP flanged base

Voltage Range: 

15 to 32 Volts DC Peak

Standby Current: 

300 µA @ 24 VDC (one communication every 5 seconds with LED blink enabled)

LED Current: 

 6.5 mA @ 24 VDC

Fixed Temperature Rating: 

135°F (57°C) H355 and H355R; 190°F (88°C) H355HT

Rate of Rise Detection: 

Responds to greater than 15°F/minute; H355R

INSTALLATION AND MAINTENANCE INSTRUCTIONS

activate the communication line.

5.  Test the sensor(s) as described in the TESTING section of this manual.

FIGURE 1. WIRING DIAGRAM:

3

2

1

3

2

1

3

2

1

(–)

(+)

+

-

UL

 LISTED COM

P

A

TIBLE

CONTROL

 P

ANEL

CAUTION: DO NOT LOOP WIRE 

UNDER TERMINAL 1 OR 2.

BREAK WIRE RUN TO PROVIDE 

SUPERVISION OF CONNECTIONS.

CLASS A OPTIONAL WIRING

REMOTE 

ANNUNCIATOR

(–)
(+)

C0129-00

FIGURE 2:

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

C0162-00

TAMPER RESISTANCE 

The sensor base includes a tamper proof feature which when activated pre-
vents  removal  of  the  sensor  without  the  use  of  a  tool.  See  the  installation 
instruction manual for the sensor base for details in using this feature.

TESTING SENSITIVITY

Before  testing,  notify  the  proper  authorities  that  the  system  is  undergoing 
maintenance,  and  will  temporarily  be  out  of  service.  Disable  the  system  to 
prevent unwanted alarms. 

All sensors must be tested after installation and periodically thereafter. Test-
ing  methods  must  satisfy  the  Authority  Having  Jurisdiction  (AHJ).  Sensors 

One FireLite Place

Northford, CT 06472

Phone: 203.484.7161 