S5 DIP Switch Settings
16
Document #50580 Rev.C 8/12/97 P/N 50580:C
•
Switch 5 - used to determine if the tone selected by S1 switches 2 and 3 will be generated after the message is
transmitted:
OFF = No tone after message
ON = Tone after message (factory default setting)
•
Switch 6, 7 and 8 - used to determine the number of times the voice message will repeat.
2.2
S5 DIP Switch Settings
•
Switch 1 - Future use
•
Switch 2 - Provides two distinct functions for message recording and speaker circuit selection as follows:
Message Recordings:
When recording a message to be played back by the Digital Message Generator, Switch 2 is used to
set the number of messages to be recorded:
OFF = one 60 second 'fire' message (factory default setting).
Note: Can also be recorded as one evacuate message in two languages; one language recorded imme-
diately after the first language.
ON = two 30 second messages.
Note: Both messages can be 'fire' related or one may be 'nonfire' related, i.e. 'fire evacuation' and 'fire
clear' messages or 'fire' and 'tornado warning' messages.
Speaker/Message Selection
During panel operation, Switch 2 is also used to determine which speaker circuit(s) will be activated
by Command Input Circuits 1 & 2 and which message will be transmitted. In order for the speaker
circuit select function to operate, be certain to install the second amplifier and do not select the backup
feature.
1. Some jurisdictions require tone evacuate only. This option prevents voice messages
from being generated. Verify with local AHJ if voice message is allowed and the num-
ber of times the message may be repeated.
TABLE 2-2:
Switch Settings for Message Repeat
SWITCH
6
SWITCH
7
SWITCH
8
NUMBER OF TIMES TO REPEAT DIGITAL
VOICE MESSAGE
OFF
OFF
OFF
Tone only, no voice
1
ON
OFF
OFF
3
OFF
ON
OFF
4
ON
ON
OFF
6 (factory default)
OFF
OFF
ON
8
ON
ON
ON
INFINITE (until FACP NAC or Manual Evacuate
switch is reset)