ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
69
Master Programming Level
Programming
Special Purpose Zone
Pressing
3
for Special Purpose, while viewing Zone Setup Screen #1, will display the following screens:
Zones 097, 098, 099, and 096 can be programmed for normal zone operation or for special purpose applications. In the above illustra-
tion, the four zones are shown Off, which means they can be programmed to function in the same manner as all other zones, by assigning
them to input and output devices in the Programming Zone Assignment Screen.
Pressing
1
will cause the display to change to
PAS 97 On
. Each press of the
1
key will cause the display to toggle between
PAS 97 On
and
PAS 97 Off
. When Zone 097 is programmed On, a PAS (Positive Alarm Sequence) activation of any smoke detector will cause Zone 097
to activate. By assigning Zone 097 to a control module in the Programming Zone Assignment Screen, an output device connected to the
control module can be used to indicate a PAS condition in the control panel.
Do not assign Zone 97 to a Notification Appliance Circuit
when using this zone to indicate a PAS condition. Attempting to do so will generate an error message and will be prevented by software
checks.
Pressing
2
will cause the display to change to
Pre-signal 98 On
. Each press of the
2
key will cause the display to toggle between
Pre-sig-
nal 98 On
and
Pre-signal 98 Off
. When Zone 098 is programmed On, a Pre-signal activation of any device will cause Zone 098 to acti-
vate. By assigning Zone 098 to a control module in the Programming Zone Assignment Screen, an output device connected to the
control module can be used to indicate a Pre-signal condition in the control panel.
Do not assign Zone 098 to a Notification Appliance
Circuit when using this zone to indicate a Pre-signal condition. Attempting to do so will generate an error message and will be prevented
by software checks.
Pressing
3
will cause the display to change to
Two Stage 99 On
. Each press of the
3
key will cause the display to toggle between
Two
Stage 99 On
and
Two Stage 99 Off
. Refer to “Two Stage Operation” on page 77 for a description of this feature.
Pressing
1
while viewing the Special Purpose Zone Screen #2 will cause the display to change to
Local Alm 96 On
. Each press of the
1
key will cause the display to toggle between
Local Alm 96 On
and
Local Alm 96 Off
. When Zone 096 is programmed On, a Local Alarm
activation of any smoke detector will cause Zone 096 to activate. By assigning Zone 096 to a control module in the Programming Zone
Assignment Screen, an output device connected to the control module can be used to indicate a local alarm condition in the control
panel.
Local Alarm Zone alarms are not reported to the Central Station.
Zones Installed
Pressing
1
for Zones Installed, while viewing Zone Setup Screen #2, will display a screen similar to the fol-
lowing:
This display will show all of the zones that have been programmed into the control panel. Note that an up and/or down arrow may appear
in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to
view the additional zones.
Zones Enabled
Pressing
2
for Zones Enabled, while viewing Zone Setup Screen #2, will display a screen similar to the following:
This display will show all of the zones that are enabled in the control panel. Note that an up and/or down arrow may appear in the upper
right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view the
additional zones.
Zones Disabled
Pressing
3
for Zones Disabled, while viewing Zone Setup Screen #2, will display a screen similar to the following:
SPECIAL PURPOSE
1=PAS 97 OFF
2=PRESIGNAL 98 OFF
3=TWO STAGE 99 OFF
Special Purpose Zone Screen #1
SPECIAL PURPOSE
1=LOCAL ALM 96 OFF
Special Purpose Zone Screen #2
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zone Setup Screen #2
ZONES INSTALLED
000 001 002 003 004
005
Zones Installed Screen
ZONES ENABLED
000 001 002 004 005
006 007 008 009 010
011 012 013 014 015
Zones Enabled Screen
ZONES DISABLED
003
Zones Disabled Screen
Содержание ES-200X
Страница 137: ...ES 200X Series Manual P N LS10131 000FL E C 7 25 2018 137 Notes ...
Страница 164: ...164 ES 200X Series Manual P N LS10131 000FL E C 7 25 2018 ...
Страница 166: ...Cut along dotted line ...
Страница 168: ...One Fire Lite Place Northford CT 06472 1601 USA USA Phone 203 484 7161 Canada Phone 905 856 8733 www firelite com ...