REAR TERMINAL VIEW

Wall Installation

Pull the electrical cables through liquid tight connectors.

Use electrical cables with the proper external diameter for the liquid tight 

connector.

PG11/PG9: external diameter between 2-7 mm (0.079-0.276”)

Refer to dedicated sensor manual for its wiring.

• Remove the upper part of the terminals for an easy cabling.

• Insert wire tip or ferrule completely into the terminal and fix with the screw 

until finger tight.

• Do not route the sensor and DC power, cables in conduit containing AC 

power wiring. Electrical  noise may interfere with sensor signal.

• Routing the sensor cable in grounded metal conduit can help prevent 

electrical noise and mechanical damage.

• Seal the cable entry points to prevent moisture damage.

• In case of malfunctioning of the instrument due to radio interferences, use 

shielded cables and on the DC power cable is suggested to apply the ferrite 

producing two opposite (180 °) coils on both wires (positive and negative)

POWER WIRING DIAGRAM

Power Supply   

12 - 24 VDC   
12 - 24 VDC   

+ VDC   

- VDC   

2   
1   

Содержание FLS M9.50 Series

Страница 1: ...h it Product installation and wiring connections should only be performed by qualified staff Do not modify product construction Installation and Commissioning Statements Remove power to the instrument before wiring input and output connections Do not exceed maximum specifications using the instrument To clean the unit use only chemical compatible products Please verify that the product is complete...

Страница 2: ...lated to specific calibration factors maximizes system flexibility guaranteeing highest level of accuracy A proper package of outputs grants to control and to monitor the batching system remotely TECHNICAL DATA General Associated sensors FLS hall effect flow sensors with frequency output or FLS F6 60 flow magmeter family Materials Case ABS Display window PC Panel Wall gasket silicone rubber Keypad...

Страница 3: ...g signal alarm 2 x Relay output Mechanical SPDT contact Expected mechanical life min operations 107 Expected electrical life min operations 105 N O N C switching capacity 5A 240VAC Max pulse min 60 Hysteresis User selectable User selectable as OUT1 Option Two stage shutdown Source Solution Volume Warning overrun or missing signal alarm OUT2 Batch Batch in progress indication Environmental Operatin...

Страница 4: ...l version is installed using the panel mounting kit M9 SN1 while the wall mounting version is got fixing the panel mounting version on the wall mounting kit M9 KWX The mounting kits can be ordered directly connected to the monitor or separately and then simply installed on it DIMENSIONS INSTALLATION PANEL MOUNTING WALL MOUNTING ...

Страница 5: ...onnectors of cables internally mount caps on screw sites to get a IP65 watertight installation WIRING General recommendation Always ensure the power supply is switched off before working on the device Make wiring connections according to wiring diagrams Terminals accept 26 to 12 AWG 0 08 to 2 5 mm2 Strip around 10 mm 0 4 of insulation from the wire tips and tin bare ends to avoid fraying Ferrules ...

Страница 6: ...ith the screw until finger tight Do not route the sensor and DC power cables in conduit containing AC power wiring Electrical noise may interfere with sensor signal Routing the sensor cable in grounded metal conduit can help prevent electrical noise and mechanical damage Seal the cable entry points to prevent moisture damage In case of malfunctioning of the instrument due to radio interferences us...

Страница 7: ...S website www flsnet it on product profile Max voltage rating 5A 240 VAC resistive load To reduce the possibility of noise interference do not route signal cables together with AC power cable Mechanical switch contact like in the drawing RELAY 2 Flow Flow AC or DC Power NC COM NO 12 11 10 STOP START RESUME RESUME GND START STOP 18 17 19 20 RELAY1 OPTION RELAY WIRING DIAGRAM A Two Stage Shutdown Op...

Страница 8: ...24 VDC MAX pull up voltage To reduce the possibility of noise interference do not route signal cables together with AC power cable Same connections for SSR 2 RELAY 1 NC COM NO 12 11 10 AC or DC Power Alarm Device SSR 1 COM NO 4 3 AC or DC Power Alarm Device Optically isolated 50 mA MAX sink 24 VDC MAX pull up voltage To reduce the possibility of noise interference do not route signal cables togeth...

Страница 9: ...ase a set alarm is activated OVERRUN AND MISSING SIGNAL ALARM always with priority a green backlight during the batch perfoming The SOURCE SOLUTION VOLUME WARNING doesn t affect the backlight color The M9 50 is able to store 10 different batches with 10 different correlated k factors 1 Click to start batch 2 Only in case Source Solution Volume Warning has been activated VIEW LEVEL NOT RUNNING Volu...

Страница 10: ...me Warning has been activated 4 Resettable totalizers can be reset using on view level VIEW LEVEL NOT RUNNING MENU DIRECTORY Volume batch Batch volume calibration 3 Compensation value Totalizer 4 Item Code Software Release To select batch number 5 Source solution volume in liters percentage 6 Settings Calibration Outputs Options Setting view ...

Страница 11: ...EVEL Compensation 7 Auto Calibration 7 Custom K factor 7 Installation Data Flow Unit Volume Unit 1 SSR 2 SSR 1 RELAY Test Output Language Asec Filter Counter Backlight Default Data Flow Rate Decimal Point Password 8 Contrast Outputs Activation to modify an item to scroll right to return to Menu without saving to save new settings Sensor Type Pipe Parameter Pipe Diameter Internal Diameter K factor ...

Страница 12: ...t is enabled a icon will appear In case a digital output is set icon reports the operating mode In case set digital output is activated the icon will turn to black display turns green in case output is set to manage an external device red to indicate a activated output as alarm L s ENTER TO START BATCH 10 000 10 000 BATCH L BATCH BATCH 0 000 0 000L L s ENTER TO START BATCH 10 000 10 000 BATCH L BA...

Страница 13: ...ch At the end of the last Batch monitor has to be reset locally no remote reset allowed No flow detected during batch operation after a set timing period TWO STAGE SHUTDOWN green backlight icon reports TWO SOURCE SOLUTION VOLUME WARNING icon reports SSW NO SIGNAL ALARM red backlight icon reports NOS OVERRUN ALARM red backlight icon reports OVR ON ON OFF OFF Relay Batch Time 0 OUT 2 Option Relay OU...

Страница 14: ...he end of the procedure restart the instruments in order to refresh M9 50 software It takes 90 seconds to refresh the SW Please do not interrupt the restarting process TO UPDATE NEW UNITS Download the interface software FLS Calibration System and the updated software on www flsnet it Launch the software FLS Calibration System on the laptop Push together ENTER and ESC powering the monitor Connect M...

Страница 15: ...requency 2 S S R 2 mech relay ACCESSORIES SPARE PARTS Part No Name Description M9 KW1 Wall mounting kit 144x144mm plastic box for wall installation of all panel mount monitors M9 KW2 Wall mounting kit with power supply 144x144mm plastic box and 110 230VAC to 24 VDC power supply for wall installation of all panel mount monitors M9 KUSB USB cable for device interfacing USB cable dedicated to FLS pro...

Страница 16: ...FIP Formatura Iniezione Polimeri S p A Loc Pian di Parata 16015 Casella Genova Italy Tel 39 010 96211 Fax 39 010 9621209 www flsnet it I2354 IMM950E REV 02 07 2016 ...