12
OUTPUT MODE
The M9.07 Dual-Parameter Conductivity and Flow Monitor & Transmitter
features 2 solid state relays and 2 mechanical relays in addition to 2 analog
output 4-20mA freely.Only the second mechanical relay can be set as a
conductivity alarm (icon is 4ALR) related to the feedback of external device
managing. Icon will turn to 4OTA (Over Time Alarm) in case the conductivity
setpoint has not been reached within set maximum timing. Icon will turn to
4OVA (Over Values Alarm) in case conductivity values overstep the set value
band. In addition to the type of failure, a reference number correlated to the
involved digital output is reported by the out put number.
PROCEDURE FOR OUTPUTS SETTING
- go to the “Options” menu
- enter into the “Outputs activation” sub menu
- enable output(s)
- go to the “Outputs” menu
- set the operating mode for each enabled output
Monitor without digital
output activated
In case a digital output
is enabled, a icon will
appear
In case a digital output
is set, icon reports the
operating mode
In case set digital
output is activated, the
icon will turn to black
mS
ENTER TO CONFIGURE
ENTER TO CONFIGURE
1 OFF
mS
ENTER TO CONFIGURE
1 PRP
mS
ENTER TO CONFIGURE
1 PRP
mS
EDIT LEVEL
PUSH BUTTON
to modify an item
to scroll right
to return to Menu without saving
to save new settings
↓
↓