"Mini Finn" Heater Installation & Operation Instructions
DIAGRAM 1
2 pcs
Backing
board
6 pcs
15" B C
50"
min.
75"
min.
5" min.
Wall mounting bracket
A
Figure 1A 1B 1C
Refer to the drawings below (figs. 1A, 1B, &
1C) for the proper clearances to combustible
materials
.
DIAGRAM 2
DIAGRAM 3
MIN. DISTANCE FOR THE
MOUNTING BRACKET AND TO
COMBUSTIBLE MATERIAL
B
Page 2
3" min.
"A"
DISTANCE
"B"
DISTANCE
"C"
DISTANCE
21T
3"
1 1/4"
1 1/4"
30T
3"
1 1/4"
2 1/2"
HEATER
MINIMUM
Floor Area
Ceiling
Height
Volume
Cu.Ft.
Ceiling
Height
Volume
Cu.Ft.
2.1
8 sq. ft.
75"
45
84"
100
1
240
12.5
12-2 W/G
120
17.5
12-2 W/G
120
25
10-2 W/G
FU30
1202-30-17
3
8 sq. ft.
75"
70
84"
150
1
84"
150
1
3
8 sq. ft.
75"
70
VAC
AMPS
WIRE
SIZE
FU21
1202-21-17
KW
MINIMUM ROOM
MAXIMUM ROOM
PHASE
HEATER
MODEL
Product Number
FU30
1202-30-17