User’s Manual 7M
57
RESET, RESTART M-BUS MC350 VIA PRIMARY/SECONDARY ADDRESS (SND_UD
This Telegram reset/restarts M-BUS MC350. The M-BUS 7M.38.8.400.XXXX confirms correct receipt by ACK.
If the telegram was not correctly received the M-BUS 7M.38.8.400.XXXX will not send an acknowledgement.
M-BUS TELEGRAM
TOTAL ENERGY COUNTERS 0, 1, 2, 3
Energy counters could represent: +/- active energy, +/-reactive energy or apparent energy and one of 4-th tariff.
ACTIVE TARIFF NUMBER
Tariff number in progress (1 to 4)
ACTIVE POWER TOTAL PT (W)
Active power total in 32 bit x 10
(2-3)
W
ACTIVE POWER TOTAL (KVAR)
Reactive power total in 32bit x10
(2-3)
var
INSTANT APPARENT POWER TOTAL (VA)
Apparent power total in 32 bit x 10
(5-6)
VA
POWER FACTOR: -: LEADING ET +: LAGGING: PF
Power factor as 32-bit integer * 10
-3
DIF
DIFE
DIFE
VIF
VIFE
VIFE
VIFE
DATA
xx.xx.xx.xx
T0:
04
none
none
T1:
84
10
none
T2:
84
20
none
A+:
05
none
none
none
*10
5-3
Wh
A–:
85
3C
none
none
*10
5-3
Wh
R+:
FB
82
75
none
*10
5-3
varh
R–:
FB
82
F5
3C
*10
5-3
varh
App:
FB
84
75
none
*10
5-3
VAh
DIF
DIFE
DIFE
VIF
VIFE
VIFE
VIFE
DATA
01
FF
01
xx
DATA: value represent as 8-bit integer
DIF
DIFE
DIFE
VIF
VIFE
DATA
04
2A
01
xx.xx.xx.xx
DIF
DIFE
VIF
VIFE
VIFE
VIFE
DATA
04
FB
97
72
xx.xx.xx.xx
DIF
DIFE
VIF
VIFE
VIFE
VIFE
DATA
04
FB
B4
75
xx.xx.xx.xx
n - 0…7
DIF
DIFE
DIFE
VIF
VIFE
VIFE
VIFE
DATA
04
A8
B4
35
xx.xx.xx.xx
Unit : W/V/A