3. Reactive power control

The inverter provides several modes of operation for reactive power control 

and are described below:

• Disable: This is the default setting. Under this setting, the inverter exports 

with a power factor of 1.0.

• 

Fixed power factor control (Cosɸ set): In this mode, the operator can set 

the output power factor to a fixed value. When enabled, a new value will 

be set in the inverter.

• Q Fixed (Q Set): Sets the reactive power to a fixed value. When enabled, 

a new value will be set in the inverter.

• 

Power factor as function of output power (Watt/Cosφ Settings: Cosφ(P)): 

In this mode, the inverter reduces the power factor (cos-phi) as a function 

of the output power at a given operating point. The 4 points of the default 

curve, where you can set the % of Pmax values and related cos-phi, can 

be modified using the internal Webserver. When enabled, the curve will 

be set in the inverter.

• Dynamic Volt/VAR control (Volt/VAr Settings: Q(V)): Under this mode, 

the level of reactive power exported by the inverter is a function of the 

operating grid voltage, also known as a Volt/VAR curve. The 4 points of 

the default curve, where you can set the % of Vnom values and related % 

of Smax, can be modified using the internal Webserver. When enabled, 

the curve will be set in the inverter.

4. Active Power Control

This inverter offers several modes for active power reduction.

• Active Power Curtailment: Sets a new value of active power as % of 

Pmax. When enabled, a new value will be set in the inverter. 

• CEI Average VGrid Derating (only italian grid standard): Sets, after a 

specific threshold, an active power derating based on the average of Vac 

on 10 minutes as per CEI-021 italian grid standard.

• Volt/Watt settings: P(V). Under this mode, the level of active power 

exported by the inverter is a function of the operating grid voltage, also 

known as a Volt/Watt curve. The 4 points of the default curve, where you 

can set the % of Vnom values and related % of Pmax, can be modified 

using the internal Webserver. When enabled, the curve will be set in the 

inverter.

• Frequency/Watt function (Frequency Control: P(f)): In this mode, the 

inverter limits the active power as a function of the grid frequency.  

5.  Ramp control

The inverter is designed to control the rate at which output power is 

increased, either at startup, or after a temporary low power condition on the 

PV array (such as fast shading). The following ramp controls are provided 

on this inverter.

• Normal ramp: The normal ramp defines the maximum rate at which the 

inverter can increase the output power under normal operation. The 

normal ramp control limits the fluctuations in the output power in order to 

prevent instabilities on the utility grid.

• Soft start: The soft-start ramp defines the maximum rate at which the 

inverter can increase the output power when the inverter is first starting 

up. This startup may occur on a daily basis or when the inverter restarts 

after an abnormal grid event has ended.

  READ THE MANUAL  – 

E

Refer to the dedicaterd application note 

in the FIMER Solar website for more details about the grid support 

functions.

For more information 

please contact 

your local FIMER 

representative or visit:

fimer.com

We reserve the right to make technical changes or 

modify the contents of this document without prior notice. 

With regard to purchase orders, the agreed particulars 

shall prevail. FIMER does not accept any responsibility 

whatsoever for potential errors or possible lack of 

information in this document.

We reserve all rights in this document and in the 

subject matter and illustrations contained therein. Any 

reproduction, disclosure to third parties or utilization of 

its contents – in whole or in parts – is forbidden without 

prior written consent of FIMER. Copyright© 2020 FIMER. 

All rights reserved.

26-04-2021

Содержание UNO-DM-3.3-TL-PLUS-US-SB-RA-Q

Страница 1: ... product manual from www fimer com Choose the correct country string inverters single phase choose the product and proceed to the download section Read and follow all safety and installation instructions to avoid disabling any safety features or making the warranty invalid APPLY HERE THE WIRELESS IDENTIFICATION LABEL ...

Страница 2: ...ions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation 2 ModelsandInverterComponents This installation guide covers 4 inverter models of different power levels 3 3 kW 3 8 kW 4 6 kW and 5 0kW For each model the following variant is available UNO DM 3 3 TL PLUS US SB RA Q UNO DM 3 8 TL PL...

Страница 3: ...ting 6 in 4 in 4 in 8 in NO OK NO OK OK OK OK OK OK OK OK 5 MAX 5 MAX NO NO NO OK NO OK OK OK OK OK OK OK OK ATTENTION A Do not block access to the external AC and DC disconnects NOTE D Please refer to the warranty terms and conditions and avoid voiding the warranty with improper installation 4 Mounting Instructions Mount the inverter following the step by step procedure below ATTENTION A Do not r...

Страница 4: ... This is the responsibility of the installer WARNING B Confirm that the maximum PV array short circuit current for each DC input channel is within the inverter specification see table in Section 14 Array equipment grounding must be installed per the requirements of the NEC and is the responsibility of the installer A configuration program that can help to correctly size the photovoltaic system is ...

Страница 5: ...phases in order to reduce power imbalance between the phases When all connections are complete reinstall the front covers and tighten the cover screws with 1 5Nm 13 2 in lbs torque 9 User Interface LEDs in various combinations may show the status conditions or perform complex actions to be explored by consulting the product manual LEDs 06 POWER Green Solid when the inverter is working correctly Fl...

Страница 6: ... vary for reasons connected to the wireless home router setup for example a very brief DHCP lease time If verification of the address is required it is usually possible to obtain the client list and the corresponding IP addresses from the wireless router administration panel If the inverter loses the connection with the home wireless network it is available accessing the Wi Fi network ABB XX XX XX...

Страница 7: ...red by NFPA 70 Article 690 11 is provided by the inverter The AFD performs a self test when the system is started If the self test results are OK the inverter will continue to AC grid connection If a potential problem on the AFD board is detected the self test will result in error E053 During normal operation the input current is continually measured and analyzed If a DC arc fault is detected duri...

Страница 8: ...ported by the inverter is a function of the operating grid voltage also known as a Volt Watt curve The 4 points of the default curve where you can set the of Vnom values and related of Pmax can be modified using the internal Webserver When enabled the curve will be set in the inverter Frequency Watt function Frequency Control P f In this mode the inverter limits the active power as a function of t...

Отзывы: